Thermo Products OD6FA072DV5B, OD6FA072DV5R, OD6RX072DV5R, OD6RA072DV5B Motor Blower Speed

Models: OD6FA072D48B OD6FA072DV5B OD6RA075DV5R OD6FA072D48R OD6RA072D48R OD6RA072D48B OD6FX072DV5R OD6RA072DV5B OD6RX072DV5R OD6FA072DV5R

1 76
Download 76 pages 60.97 Kb
Page 38
Image 38
Motor Blower Speed

DIP SWITCH 2 SECTION STATE

BLOWER DELAY TIMES

 

1

2

3

4

Counter Flow

ON - SEC

 

OFF - MIN

ON - SEC

 

 

 

 

 

 

 

 

OFF

OFF

 

 

15

30

 

 

 

 

 

 

 

 

 

 

ON

OFF

 

 

24

60

 

 

 

 

 

 

 

 

 

 

OFF

ON

 

 

36

120

 

 

 

 

 

 

 

 

 

 

ON

ON

 

 

48

240

 

 

 

 

 

 

 

 

 

 

 

 

OFF

OFF

 

 

 

2

 

 

 

 

 

 

 

 

 

 

ON

OFF

 

 

 

4

 

 

 

 

 

 

 

 

 

 

OFF

ON

 

 

 

6

 

 

 

 

 

 

 

 

 

 

ON

ON

 

 

 

8

 

 

 

 

 

 

 

 

Table 11: ON and OFF Blower Delay Time Switch Settings

Motor Blower Speed

Three interconnected blower speed outputs are provided. A “G” call for fan will provide power to the LOW speed tap only. A “W” heat call will provide power to the Heat speed tap only. A “Y” cooling call will provide power to the Cool speed tap only.

In the case of thermostat calls for “Y” and “W” together, blower speed selection will be determined by the input that was first initiated. In the case where the control is in a cooling mode with both “Y” and “W” inputs energized and then the “Y” input is removed, the cooling blower off time will be executed prior to the control switching into a heating mode. In the case where the control is in a heating mode with both “Y” and “W” inputs energized and then the “W” input is removed, the heating blower off time will be executed prior to the control switching into a cooling mode. In the case where a call for fan “G” already exists and either a “W” or a “Y” call is initiated, the blower speed will switch to the respective “W” or a “Y” speed following the blower on delay for that call.

The speed taps are interconnected and interlocked, only one speed may be powered at any one time. When a speed is to be operated, the speed select relays are operated to select the path to the motor tap and then the enable relay is operated to switch the operating power to the selected motor speed tap. If the speed of the running motor is to be changed, first the enable relay removes power from the motor, the new speed is selected and then power is restored to the motor.

Counterflow Operation

Counter flow operation will be allowed if JW10 is cut. If JW10 is not cut, the control will not perform any of the Counter Flow Operation as described below. Counter Flow Operation is only valid when a call for Heat is present.

Counter Flow Operation will bring the blower on at a defined low speed at a defined time between the enabling of the burner and the selected turn on time delay. Turn on delay times for the Counter Flow Operation are defined in Table 11. For PSC control, the LOW speed blower tap will be energized once the selected on delay has expired.

Once the selected Blower On Delay time has been reached, the blower operation will change to the operation described in Motor Blower Speed section.

Blower On and Off Delays

Four Heat blower on and four blower off delays are selected by two dip switches for each function. Refer to Table 11 for specific delay values.

35