For PSC systems, the ½ hp motor is equipped with 5 speeds. The unit is set for
Speed Tap\ | Furnace Airflow (CFM) vs. External Static pressure (in. WC.) |
|
| ||||
Static Pressure | 0.1 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 |
Low | 930 | 915 | 912 | 910 | 822 | 774 | 730 |
ML | 1155 | 1152 | 1130 | 1126 | 1085 | 1042 | 920 |
MH | 1442 | 1432 | 1418 | 1382 | 1334 | 1293 | 1230 |
High | 1802 | 1762 | 1705 | 1635 | 1569 | 1493 | 1428 |
| Furnace Motor Current Draw (Amps) vs. External Static pressure (in. WC.) |
| |||||
Low | 3.28 | 3.1 | 3.02 | 2.91 | 2.64 | 2.49 | 2.36 |
ML | 4.18 | 4.02 | 3.91 | 3.74 | 3.59 | 3.34 | 2.95 |
MH | 5.44 | 5.17 | 4.95 | 4.72 | 4.43 | 4.21 | 3.95 |
High | 6.61 | 6.36 | 6.04 | 5.73 | 5.46 | 5.17 | 4.9 |
|
|
|
| ||||
Speed Tap\ | High Fire Temperature Rise vs. External Static pressure (in. WC.) |
|
| ||||
Static Pressure | 0.1 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 |
Low | 90 | 91 | 91 | 92 | 101 | 108 | 114 |
ML | 72 | 72 | 74 | 74 | 77 | 80 | 91 |
MH | 58 | 58 | 59 | 60 | 62 | 64 | 68 |
High | 46 | 47 | 49 | 51 | 53 | 56 | 58 |
|
|
|
| ||||
Speed Tap\ | Mid Fire Temperature Rise vs. External Static pressure (in. WC.) |
|
| ||||
Static Pressure | 0.1 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 |
Low | 72 | 73 | 73 | 73 | 81 | 86 | 91 |
ML | 58 | 58 | 59 | 59 | 61 | 64 | 72 |
MH | 46 | 47 | 47 | 48 | 50 | 52 | 54 |
High | 37 | 38 | 39 | 41 | 42 | 45 | 47 |
|
|
|
| ||||
Speed Tap\ | Low Fire Temperature Rise vs. External Static pressure (in. WC.) |
|
| ||||
Static Pressure | 0.1 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 |
Low | 60 | 61 | 61 | 61 | 68 | 72 | 76 |
ML | 48 | 48 | 49 | 49 | 51 | 53 | 60 |
MH | 39 | 39 | 39 | 40 | 42 | 43 | 45 |
High | 31 | 32 | 33 | 34 | 35 | 37 | 39 |
Figure 19: Heating speed by input
Speed vs. color code for PSC Motor:
Low = Orange
M. Low = Red
Med = Blue
M. High = Yellow
High = Black
31