11 TEST RUN

Before test operation

WARNING

• Before turning on the power supply, carry out the following items.

1) Using 500V-megger, check there is 1Mor more between the terminal block of the power supply and the earth. If 1Mor less is detected, do not run the unit.

2) Check that all the valves of the outdoor unit are fully opened.

To protect the compressor at starting time, keep power-ON condition before 12 hours or more.

Never push the electromagnetic contactor to carry out a forced test operation. (It is very dangerous because a protective device does not work.)

How to execute test operation

Using the remote controller, check the operation in the usual operation. For the operation procedure, refer to the attached Owner’s Manual.

A forced test operation can be executed in the following procedure under condition of thermo-OFF of room temperature.

In order to prevent a serial operation, the forced test operation is released after 60 minutes and returns to the usual operation.

NOTE

Do not use a forced operation in cases other than test operation because it applies an excessive load to the air conditioner.

In case of wired remote controller

1, 5

2, 4

3

UNIT

SET CL

Procedure

 

 

Description

1

Keep

button pushed for 4 seconds or more. [TEST] is displayed

on the display part and the selection of mode in the test mode is

 

 

permitted.

 

TEST

2

Push

button.

 

 

Using

button, select the operation mode, [COOL] or [HEAT].

3

• Do not run the air conditioner in a mode other than [COOL] or [HEAT].

• The temperature controlling function does not work during test

 

operation.

 

 

• The detection of error is performed as usual.

4

After the test operation, push

button to stop the operation.

(Display part is same as procedure 1 )

 

 

 

5

Push

button to cancel (release from) the test operation mode.

([TEST] disappears on the display part and the status returns to a

 

normal stop status.)

 