Toshiba MMK-AP0092H Refrigerant Piping, Connection of refrigerant pipe, B Unit mm, Requirement

Models: MMK-AP0092H MMK-AP0072H MMK-AP0122H

1 29
Download 29 pages 40.58 Kb
Page 14
Image 14
8 REFRIGERANT PIPING

8 REFRIGERANT PIPING

• Projection margin in flaring :

B

B (Unit : mm)

 

Rigid (Clutch type)

Outer diam. of

R410A tool used

Conventional tool used

 

 

 

 

copper pipe

R410A

R22

R410A

R22

 

 

 

 

 

 

6.4

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

9.5

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

12.7

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

15.9

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

Imperial (Wing nut type)

Outer diam. of copper pipe

R410A

R22

 

 

 

6.4

1.5 to 2.0

1.0 to 1.5

 

 

 

9.5

1.5 to 2.0

1.0 to 1.5

 

 

 

12.7

2.0 to 2.5

1.5 to 2.0

 

 

 

15.9

2.0 to 2.5

1.5 to 2.0

 

 

 

Connection of refrigerant pipe

Connect all the refrigerant pipes with flare connecting work.

Since the atmospheric pressure only is sealed as the sealing gas, it is not abnormal that “Pushu…” sound is not heard when the flare nut is removed.

Be sure to use a double spanner for pipe connecting work of the indoor unit.

Work using double spanner

• Refer to the following table for tightening torque.

Connecting pipe

Tightening torque

Re-tightening

outer dia. (mm)

(N•m)

torque (N•m)

 

 

 

Ø6.4

14 to 18

18

(1.4 to 1.8 kgf•m)

(1.8 kgf•m)

 

 

 

 

Ø9.5

33 to 42

42

(3.3 to 4.2 kgf•m)

(4.2 kgf•m)

 

 

 

 

Ø12.7

50 to 62

50

(5.0 to 6.2 kgf•m)

(5.0 kgf•m)

 

 

 

 

Ø15.9

68 to 82

68

(6.8 to 8.2 kgf•m)

(6.8 kgf•m)

 

 

 

 

Airtight test/Air purge, etc.

For airtight test, air purge, addition of refrigerant, and gas leak check, follow the Installation Manual attached to the outdoor unit.

Open fully valves of the outdoor unit

Gas leak check

Check with a leak detector or soap water whether gas leaks or not, from the pipe connecting section or cap of the valve.

REQUIREMENT

Use a leak detector manufactured exclusively for HFC refrigerant (R410A, R134a, etc.).