FILE NO. SVM-10019

11-4-2 Caution at Servicing

1.After using the service mode of remote controller finished, press the [ ] button to reset the remote controller to normal function.

2.After finished the diagnosis by the remote controller, turn OFF power supply and turn its ON again to reset the air conditioner to normal operation. However, the check codes are not deleted from memory of the microcomputer.

3.After servicing finished, press [CLR] button of remote controller under service mode status to send code "7F" to the indoor unit. The check code stored in memory is cleared.

 

 

 

Table 11-4-1

 

 

 

 

 

 

 

 

 

 

 

Block distinction

 

Operation of diagnosis function

 

 

 

 

 

 

 

 

 

 

 

Check

 

Check

 

Air

Display flashing

 

Action and Judgment

Block

Cause of operation

conditioner

 

 

 

code

code

error

 

 

 

 

status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor P.C.

 

TA sensor ; The room

Operation

Flashes when

1.

Check the sensor TA and connection.

 

board.

 

temperature sensor is

continues.

error is detected.

2.

In case of the sensor and its

 

 

 

short-Circuit or disconnection.

 

 

 

connection is normal, check the

 

 

 

 

 

 

 

P.C. board.

 

 

 

 

 

 

 

 

 

 

 

TC sensor ; The heat

Operation

Flashes when

1.

Check the sensor TC and connection.

 

 

 

exchanger temperature

continues.

error is detected.

2.

In case of the sensor and its

 

 

 

sensor of the indoor unit

 

 

 

connection is normal, check the

 

 

 

is out of place, disconnection,

 

 

 

P.C. board.

 

 

 

short-circuit or migration.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan motor of the indoor unit

All OFF

Flashes when

1.

Check the fan motor and connection.

 

 

 

is failure, lock-rotor, short-

 

error is detected.

2.

In case of the motor and its

 

 

 

circuit, disconnection, etc.

 

 

 

connection is normal, check the

 

 

 

Or its circuit on P.C. board

 

 

 

P.C. board.

 

 

 

has problem.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Other trouble on the indoor

Depend on

Depend on

Replace P.C. board.

 

 

 

P.C. board.

cause of

cause of

 

 

 

 

 

 

failure.

failure.

 

 

 

 

 

 

 

 

 

 

– 71 –