FILE NO. SVM-10019

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

Operation flow and applicable data, etc.

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

 

Capacity

The cooling or heating capacity depending on the load is

1) The difference between set

 

 

control

adjusted.

 

 

 

 

 

 

 

temperature on remote controller

 

 

 

 

 

According to difference between the setup value of tempera-

(Ts) and room temperature (Ta)

 

 

 

 

 

ture and the room temperature, the capacity is adjusted by

is calculated.

 

 

 

 

 

 

 

the compressor revolution.

 

 

 

2) According to the temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

difference, the correction value of

 

 

 

Remote contr oller

 

 

 

Indoor unit

 

 

 

Hz signal which determines the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

compressor speed is set up.

 

 

 

Set temp. (Ts)

 

 

 

Room temp. (Ta)

 

 

 

 

 

 

 

 

 

3) The rotating position and speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of the motor are detected by the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

electromotive force occurred on

 

 

 

 

 

 

 

 

 

Ts Ta

 

 

 

 

 

 

 

the motor winding with operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of the compressor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4) According to the difference

 

 

 

 

 

 

 

Correction value of Hz signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

resulted from comparison of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

correction value of Hz signal with

 

 

 

 

 

 

Detection of electromotive force

 

 

 

 

the present operation Hz, the

 

 

 

 

 

 

 

of compressor motor winding

 

 

 

 

inverter output and the commuta-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tion timing are varied.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5) Change the compressor motor

 

 

 

 

 

 

Detection of motor speed (Operation Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

speed by outputting power to the

 

 

 

 

 

 

 

 

and rotor position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

compressor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* The contents of control

 

 

 

 

 

Correction value of Hz signal-Operating Hz

 

 

 

 

 

 

 

 

 

 

 

operation are same in cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation and heating

 

 

 

 

 

 

 

 

Inverter output change

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

Commutation timing change

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Change of compressor speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.

 

Current release

This function prevents troubles on the electronic parts of the

1) The input current of the outdoor

 

 

control

compressor driving inverter.

 

 

 

unit is detected in the inverter

 

 

 

 

 

This function also controls drive circuit of the compressor

section of the outdoor unit.

 

 

 

 

 

speed so that electric power of the compressor drive circuit

2) According to the detected

 

 

 

 

 

does not exceed the specified value.

 

 

 

outdoor temperature, the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

specified value of the current is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

selected.

 

 

 

 

Outdoor unit inverter main

 

 

Outdoor temp. To

 

 

 

 

 

 

 

 

 

 

3) Whether the current value

 

 

 

circuit control current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exceeds the specified value or

 

 

 

 

 

 

 

 

 

 

 

Setup of current release point

 

 

not is judged.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4) If the current value exceeds the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

 

specified value, this function

 

 

 

Operating current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reduces the compressor speed

 

 

 

Reduce compressor speed

 

 

 

 

 

Setup value

 

 

 

 

 

and controls speed up to the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

 

 

 

 

 

 

 

 

 

 

 

 

 

closest one commanded from the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current decrease

indoor unit within the range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

which does not exceed the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity control continues

 

 

 

 

 

 

 

 

 

specified value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor temp.

Cooling current release value

 

Heating current release value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RAS-09LAV-UL

RAS-12LAV-UL

RAS-09LAV-UL

RAS-12LAV-UL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

113ºF (45ºC)

 

 

 

 

 

 

3.97A

 

 

4.27A

 

6.30A

 

7.72A

 

 

 

104ºF (40ºC)

 

 

 

111ºF (44ºC)

4.35A

 

 

4.88A

 

 

 

 

 

 

 

61ºF (16ºC)

 

 

 

102ºF (39ºC)

6.30A

 

 

8.47A

 

 

 

 

 

 

 

52ºF (11ºC)

 

 

 

60ºF (15.5ºC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51ºF (10.5ºC)

 

 

 

 

 

 

 

6.30A

 

8.10A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.30A

 

8.47A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 33 –