General Data | SCWF/SIWF |
| |
|
|
|
|
Table GD-3. SCWF/SIWF Water-Cooled Self-Contained, 42-80Tons
Unit Size |
| 42 | 46 | 52 | 58 | 65 | 72 | 80 |
Compressor Data |
|
|
|
|
|
|
|
|
Quantity |
| 2/1 | 2/1 | 3 | 3 | 3/1 | 3/1 | 4 |
NominalTon/Comp |
| 10/15 | 10/15 | 15 | 15 | 15/10 | 15/10 | 15 |
Circuits |
| 3 | 3 | 3 | 3 | 4 | 4 | 4 |
Evaporator Coil Data |
|
|
|
|
|
|
|
|
Rows |
| 3 | 4 | 2 | 4 | 3 | 4 | 6 |
Sq. Ft. |
| 38.57 | 38.57 | 49.09 | 49.09 | 49.09 | 49.09 | 49.09 |
Sq. m |
| (3.58) | (3.58) | (4.56) | (4.56) | (4.56) | (4.56) | (4.56) |
FPF |
| 144 | 144 | 144 | 144 | 144 | 144 | 144 |
Condenser Data |
|
|
|
|
|
|
|
|
Minium GPM w/o Econ |
| 64 | 64 | 84 | 84 | 102 | 102 | 112 |
Minium liters / sec. w/o Econ | (4.04) | (4.04) | (5.3) | (5.3) | (6.43) | (6.43) | (7.07) | |
Minimum GPM w/ Econ |
| 64 | 64 | 84 | 84 | 102 | 102 | 112 |
Minium liters / sec. w/ Econ |
| (4.04) | (4.04) | (5.3) | (5.3) | (6.43) | (6.43) | (7.07) |
MaximumGPM |
| 142 | 142 | 186 | 186 | 226 | 226 | 248 |
Maximum liters / sec. |
| (8.96) | (8.96) | (11.73) | (11.73) | (14.26) | (14.26) | (15.65) |
Evaporator Fan Data |
|
|
|
|
|
|
|
|
Quantity |
| 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Size (Dia. - inches) |
| 25" | 25" | 25" | 25" | 27.5" | 27.5" | 27.5" |
Size (Dia. - mm) |
| (635) | (635) | (635) | (635) | (698.5) | (698.5) | (698.5) |
MinimumHP |
| 7.5 | 7.5 | 10 | 10 | 10 | 10 | 10 |
MinimumkW |
| (5.59) | (5.59) | (7.46) | (7.46) | (7.46) | (7.46) | (7.46) |
MaximumHP |
| 30 | 30 | 50 | 50 | 50 | 50 | 50 |
MaximumkW |
| (22.37) | (22.37) | (37.29) | (37.29) | (37.29) | (37.29) | (37.29) |
Minimum Design CFM |
| 11200 | 11960 | 14250 | 15080 | 16900 | 18700 | 20800 |
Minimum Design liter / sec. |
| (5286) | (5645) | (6725) | (7117) | (7976) | (8825) | (9817) |
Maximum Design CFM |
| 17850 | 19550 | 22100 | 24650 | 27625 | 29800 | 29800 |
Maximum Design liter / sec. |
| (8424) | (9227) | (10430) | (11634) | (13038) | (14064) | (14064) |
General Data |
|
|
|
|
|
|
|
|
EER |
| 14.1 | 14.2 | 13.1 | 13.5 | 13.1 | 13.0 | 13.0 |
IPLV |
| 13.9 | 13.6 | 12.9 | 12.5 | 12.4 | 11.8 | 11.4 |
Refrigerant Charge - lbs. |
|
|
|
|
|
|
| |
Circuit A |
| 28 | 30 | 28 | 30 | 28 | 30 | 32 |
Circuit B |
| 24 | 25 | 28 | 30 | 28 | 30 | 32 |
Circuit C |
| 24 | 25 | 28 | 30 | 28 | 30 | 32 |
Circuit D |
| - | - | - | - | 24 | 25 | 32 |
Refrigerant Charge - kg |
|
|
|
|
|
|
|
|
Circuit A |
| (12.7) | (13.6) | (12.7) | (13.6) | (12.7) | (13.6) | (14.5) |
Circuit B |
| (10.9) | (11.3) | (12.7) | (13.6) | (12.7) | (13.6) | (14.5) |
Circuit C |
| (10.9) | (11.3) | (12.7) | (13.6) | (12.7) | (13.6) | (14.5) |
Circuit D |
| - | - | - | - | (10.9) | (11.3) | (14.5) |
Capacity Steps - % |
| 100/71/43/26/0 | 100/70/41/30/0 | 100/65/32/0 | 100/65/30/0 | 100/71/44/24/0 | 100/71/43/23/0 | 100/73/46/20/0 |
Filter Data |
|
|
|
|
|
|
|
|
Quantity |
| 4 | 4 | 4 | 4 | 4 | 4 | 4 |
Size (inches) |
| 16x20x2 | 16x20x2 | 16x20x2 | 16x20x2 | 16x20x2 | 16x20x2 | 16x20x2 |
Size (mm) | (406 X 508 X 51) | (406 X 508 X 51) | (406 X 508 X 51) | (406 X 508 X 51) | (406 X 508 X 51) | (406 X 508 X 51) | (406 X 508 X 51) | |
Quantity |
| 8 | 8 | 8 | 8 | 8 | 8 | 8 |
Size (inches) |
| 16x25x2 | 16x25x2 | 16x25x2 | 16x25x2 | 16x25x2 | 16x25x2 | 16x25x2 |
Size (mm) | (406 X 635 X 51) | (406 X 635 X 51) | (406 X 635 X 51) | (406 X 635 X 51) | (406 X 635 X 51) | (406 X 635 X 51) | (406 X 635 X 51) | |
Quantity |
| 2 | 2 | 2 | 2 | 2 | 2 | 2 |
Size |
| 20x20x2 | 20x20x2 | 20x20x2 | 20x20x2 | 20x20x2 | 20x20x2 | 20x20x2 |
Size (mm) | (508 X 508 X 51) | (508 X 508 X 51) | (508 X 508 X 51) | (508 X 508 X 51) | (508 X 508 X 51) | (508 X 508 X 51) | (508 X 508 X 51) | |
Quantity |
| 4 | 4 | 4 | 4 | 4 | 4 | 4 |
Size |
| 20x25x2 | 20x25x2 | 20x25x2 | 20x25x2 | 20x25x2 | 20x25x2 | 20x25x2 |
Size (mm) | (508 X 635 X 51) | (508 X 635 X 51) | (508 X 635 X 51) | (508 X 635 X 51) | (508 X 635 X 51) | (508 X 635 X 51) | (508 X 635 X 51) |
Notes:
1.Compressors areTrane 3D® scroll.
2.EER and IPV are rated in accordance to the ARI Standard
3.All units operate with
4.Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.
5.Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.
6.Filter sizes are for units without hot water or steam heating coils