Trane PKG-PRC002-EN manual Entering Water Temp Entering Air

Models: PKG-PRC002-EN

1 101
Download 101 pages 31.23 Kb
Page 55
Image 55

Performance

Water-Cooled

Data

65 Ton

 

 

 

 

 

 

Table PD-37. SCWF/SIWF 65 Gross Cooling Capacity - 26,000 cfm, 196 gpm

 

 

 

 

 

 

Entering Water Temp

 

 

 

 

 

 

 

 

 

 

 

 

Entering Air

 

 

75 F

 

 

85 F

 

 

95 F

 

EDB

EWB

 

Total

Sensible

 

Total

Sensible

 

Total

Sensible

 

F

F

 

MBh

MBh

LWT

MBh

MBh

LWT

MBh

MBh

LWT

 

62

 

744

609

84.1

715

597

93.9

686

583

103.8

75

67

 

809

480

84.8

779

468

94.6

746

455

104.5

 

72

 

879

351

85.5

845

338

95.4

810

326

105.2

 

62

 

749

726

84.1

722

711

94.0

694

692

104.0

80

67

 

809

601

84.8

778

589

94.6

746

576

104.5

 

72

 

878

471

85.5

844

459

95.4

810

447

105.2

 

62

 

780

780

84.5

756

756

94.4

730

730

104.4

85

67

 

809

721

84.8

779

708

94.6

747

695

104.5

 

72

 

877

592

85.5

844

579

95.4

808

567

105.2

 

 

Chart PD-49. SCWF/SIWF 65 Fan Performance for CV or with VFD

Chart PD-50. SCWF/SIWF 65 Fan Performance with Inlet GuideVanes

Note:

1.Fan curves include refrigerant coil and internal cabinet static losses.To determine static pressure to be used with these curves, add filter, economizer, flexible horizontal discharge and heat pressure drops to external duct static pressure.