Performance

Water-Cooled

Data

42 Ton

 

 

 

 

Table PD-23. SCWF/SIWF 42 - Economizer Full Capacity - 16,800 cfm

 

 

 

 

 

Entering Water Temp

 

 

Entering Air

 

 

45 F

 

 

55 F

 

EDB

EWB

Flow

Total

Sensible

LWT

Total

Sensible

LWT

F

F

gpm

MBh

MBh

F

MBh

MBh

F

 

 

105

438.5

393.8

53.4

274.5

274.5

60.2

 

62

126

457.1

401.7

52.3

281.4

281.4

59.5

 

 

142

468.6

406.6

51.6

285.4

285.4

59.0

 

 

105

556.7

335.0

55.6

322.8

247.5

61.1

75

67

126

591.2

348.7

54.4

339.9

253.6

60.4

 

 

142

612.2

357.2

53.6

350.8

257.5

59.9

 

 

105

711.9

281.0

58.6

462.2

193.6

63.8

 

72

126

757.8

297.9

57.0

494.2

204.4

62.8

 

 

142

786.0

308.5

56.1

513.6

211.0

62.2

 

 

105

480.2

470.5

54.1

343.0

343.0

61.5

 

62

126

494.6

484.9

52.9

351.6

351.6

60.6

 

 

142

503.3

493.6

52.1

356.5

356.5

60.0

 

 

105

566.9

426.2

55.8

354.9

346.2

61.8

80

67

126

597.1

438.3

54.5

367.9

350.9

60.8

 

 

142

615.8

445.8

53.7

375.9

353.8

60.3

 

 

105

710.3

368.9

58.5

462.7

281.8

63.8

 

72

126

756.0

386.0

57.0

493.0

291.9

62.8

 

 

142

784.0

396.7

56.0

511.9

298.3

62.2

 

 

105

545.5

545.5

55.4

411.4

411.4

62.8

 

62

126

559.4

559.4

53.9

421.6

421.6

61.7

 

 

142

567.3

567.3

53.0

427.4

427.4

61.0

 

 

105

590.8

522.7

56.3

412.7

412.7

62.9

85

67

126

616.6

533.0

54.8

423.0

423.0

61.7

 

 

142

632.5

539.5

53.9

428.9

428.9

61.0

 

 

105

712.7

457.3

58.6

479.1

374.9

64.1

 

72

126

756.0

473.6

57.0

504.7

383.5

63.0

 

 

142

782.8

483.8

56.0

520.7

388.9

62.3

Table PD-24. SCWF/SIWF 42 - Economizer Low Capacity - 16,800 cfm

 

 

 

 

 

Entering Water Temp

 

 

Entering Air

 

 

45 F

 

 

55 F

 

EDB

EWB

Flow

Total

Sensible

LWT

Total

Sensible

LWT

F

F

gpm

MBh

MBh

F

MBh

MBh

F

 

 

105

291.1

290.3

50.5

191.1

191.1

58.6

 

62

126

302.7

295.0

49.8

196.7

196.7

58.1

 

 

142

310.0

298.0

49.4

200.0

200.0

57.8

 

 

105

368.9

238.2

52.0

211.6

181.4

59.0

75

67

126

390.4

246.4

51.2

221.9

184.9

58.5

 

 

142

403.6

251.5

50.7

228.7

187.3

58.2

 

 

105

471.3

189.6

54.0

306.1

133.9

60.8

 

72

126

499.6

199.7

52.9

325.0

140.0

60.2

 

 

142

517.1

206.0

52.3

336.6

143.8

59.7

 

 

105

331.6

331.6

51.3

238.9

238.9

59.6

 

62

126

341.5

341.5

50.4

245.9

245.9

58.9

 

 

142

347.4

347.4

49.9

250.0

250.0

58.5

 

 

105

566.9

426.2

55.8

354.9

346.2

61.8

80

67

126

391.2

316.4

51.2

247.4

236.8

58.9

 

 

142

403.5

321.1

50.7

252.1

241.5

58.6

 

 

105

470.3

259.3

54.0

305.1

203.7

60.8

 

72

126

498.5

269.3

52.9

323.9

209.7

60.1

 

 

142

515.9

275.6

52.3

335.5

213.5

59.7

 

 

105

379.0

379.0

52.2

286.7

286.7

60.5

 

62

126

390.3

390.3

51.2

295.0

295.0

59.7

 

 

142

397.0

397.0

50.6

299.9

299.9

59.2

 

 

105

390.9

385.8

52.4

287.3

287.3

60.5

85

67

126

406.8

392.0

51.5

295.6

295.6

59.7

 

 

142

416.8

395.8

50.9

300.5

300.5

59.2

 

 

105

469.3

328.9

53.9

313.2

276.2

61.0

 

72

126

497.4

338.8

52.9

328.7

281.3

60.2

 

 

142

514.8

345.1

52.3

338.5

284.5

59.8

46

PKG-PRC002-EN

Page 46
Image 46
Trane PKG-PRC002-EN manual 42 Ton, Table PD-24. SCWF/SIWF 42 Economizer Low Capacity 16,800 cfm

PKG-PRC002-EN specifications

The Trane PKG-PRC002-EN is a groundbreaking packaged rooftop unit designed to meet the diverse needs of commercial and industrial spaces. This model showcases Trane’s commitment to innovation, energy efficiency, and reliability, making it a preferred choice for HVAC professionals and building owners alike.

One of the main features of the PKG-PRC002-EN is its high-efficiency design. This unit leverages advanced technologies to minimize energy consumption while ensuring optimal cooling and heating performance. Its efficient compressor, coupled with enhanced heat exchangers, significantly reduces operating costs and energy bills, aligning with today’s sustainability goals.

The PKG-PRC002-EN features a robust and durable construction, which translates to enhanced longevity and reduced maintenance requirements. Designed for ease of installation, the unit is compact and lightweight, facilitating seamless retrofitting and integration into existing systems. Furthermore, its accessible service panels allow for straightforward maintenance and repairs, thus minimizing downtime and service disruptions.

Equipped with Trane's advanced control technology, the PKG-PRC002-EN offers precise temperature management, ensuring consistent comfort across different zones within a building. The intuitive controls enable users to program schedules and adjust settings based on their specific needs, enhancing comfort while maximizing efficiency.

The model also incorporates advanced filtration options, improving indoor air quality by effectively reducing pollutants and allergens. This focus on health and safety is essential, especially in commercial settings where air quality can significantly impact occupant well-being and productivity.

Another notable characteristic of the PKG-PRC002-EN is its low noise levels during operation, which is essential for maintaining a conducive indoor environment in workplaces, retail spaces, or educational institutions. The unit's design minimizes sound transmission, creating a more pleasant atmosphere for occupants.

In summary, the Trane PKG-PRC002-EN is a highly efficient, reliable, and user-friendly rooftop unit that combines advanced technology with robust construction. Its energy-saving features, superior air quality options, and focus on quiet performance make it an excellent choice for modern commercial HVAC applications, ultimately contributing to sustainable building practices and enhanced occupant comfort.