Performance

Water-Cooled

Data

65 Ton

 

 

 

 

Table PD-35. SCWF/SIWF 65 - Economizer Full Capacity - 26,000 cfm

Entering Water Temp

Entering Air

 

 

45 F

 

 

55 F

 

EDB

EWB

Flow

Total

Sensible

LWT

Total

Sensible

LWT

F

F

gpm

MBh

MBh

F

MBh

MBh

F

 

 

163

644.4

590.0

52.9

407.4

407.4

60.0

 

62

195

670.0

600.7

51.9

417.5

417.5

59.3

 

 

226

689.7

609.0

51.1

424.7

424.7

58.8

 

 

163

815.9

497.6

55.0

472.6

370.1

60.8

75

67

195

863.7

516.4

53.9

495.9

378.4

60.1

 

 

226

899.9

530.8

53.0

514.5

385.0

59.6

 

 

163

1043.3

413.8

57.8

676.7

285.8

63.3

 

72

195

1106.7

436.7

56.4

720.4

300.4

62.4

 

 

226

1155.0

454.5

55.2

753.5

311.5

61.7

 

 

163

710.6

695.5

53.7

509.0

509.0

61.2

 

62

195

730.5

715.4

52.5

521.6

521.6

60.3

 

 

226

745.5

730.4

51.6

530.5

530.5

59.7

 

 

163

830.6

636.1

55.2

522.6

520.8

61.4

80

67

195

872.3

652.6

53.9

540.3

527.1

60.5

 

 

226

904.5

665.4

53.0

553.9

532.0

59.9

 

 

163

1041.0

546.6

57.8

676.9

419.8

63.3

 

72

195

1104.0

569.9

56.3

718.5

433.6

62.4

 

 

226

1152.2

588.1

55.2

750.9

444.5

61.6

 

 

163

809.6

809.6

54.9

610.6

610.6

62.5

 

62

195

829.9

829.9

53.5

625.5

625.5

61.4

 

 

226

844.4

844.4

52.5

636.1

636.1

60.6

 

 

163

867.7

783.1

55.6

612.4

612.4

62.5

85

67

195

903.1

797.2

54.3

627.4

627.4

61.4

 

 

226

930.4

808.2

53.2

638.2

638.2

60.6

 

 

163

1043.6

680.9

57.8

701.3

561.3

63.6

 

72

195

1103.6

703.1

56.3

736.1

573.0

62.5

 

 

226

1149.9

720.5

55.2

763.4

582.1

61.8

Table PD-36. SCWF/SIWF 65 - Economizer Low Capacity - 26,000 cfm

Entering Water Temp

Entering Air

 

 

45 F

 

 

55 F

 

EDB

EWB

Flow

Total

Sensible

LWT

Total

Sensible

LWT

F

F

gpm

MBh

MBh

F

MBh

MBh

F

 

 

163

420.9

405.9

50.2

278.1

278.1

58.4

 

62

195

436.1

433.3

49.5

285.8

285.8

57.9

 

 

226

448.0

438.2

49.0

291.4

291.4

57.6

 

 

163

531.1

347.9

51.5

304.3

266.3

58.7

75

67

195

559.7

358.7

50.7

317.8

271.0

58.3

 

 

226

581.7

367.0

50.1

329.0

274.9

57.9

 

 

163

678.2

274.0

53.3

440.0

194.2

60.4

 

72

195

715.9

287.3

52.3

464.9

202.3

59.8

 

 

226

744.8

297.6

51.6

484.1

208.5

59.3

 

 

163

482.5

482.5

50.9

347.6

347.6

59.3

 

62

195

496.2

496.2

50.1

357.2

357.2

58.7

 

 

226

506.4

506.4

49.5

364.2

364.2

58.2

 

 

163

535.3

453.2

51.6

348.2

348.2

59.3

80

67

195

561.0

463.0

50.8

358.2

342.1

58.7

 

 

226

581.3

470.7

50.1

365.8

349.7

58.2

 

 

163

676.7

377.8

53.3

438.6

298.1

60.4

 

72

195

714.3

391.0

52.3

463.4

306.1

59.8

 

 

226

743.2

401.3

51.6

482.5

312.3

59.3

 

 

163

551.5

551.5

51.8

417.1

417.1

60.1

 

62

195

567.1

567.1

50.8

428.5

428.5

59.4

 

 

226

578.6

578.6

50.1

436.9

436.9

58.9

 

 

163

564.7

547.6

51.9

417.9

417.9

60.1

85

67

195

585.6

575.9

51.0

429.3

429.3

59.4

 

 

226

602.0

582.2

50.3

437.7

437.7

58.9

 

 

163

675.3

481.4

53.3

450.5

406.1

60.5

 

72

195

712.8

494.6

52.3

470.8

412.7

59.8

 

 

226

741.5

504.8

51.6

486.9

417.9

59.3

54

PKG-PRC002-EN

Page 54
Image 54
Trane PKG-PRC002-EN manual 65 Ton, Table PD-36. SCWF/SIWF 65 Economizer Low Capacity 26,000 cfm

PKG-PRC002-EN specifications

The Trane PKG-PRC002-EN is a groundbreaking packaged rooftop unit designed to meet the diverse needs of commercial and industrial spaces. This model showcases Trane’s commitment to innovation, energy efficiency, and reliability, making it a preferred choice for HVAC professionals and building owners alike.

One of the main features of the PKG-PRC002-EN is its high-efficiency design. This unit leverages advanced technologies to minimize energy consumption while ensuring optimal cooling and heating performance. Its efficient compressor, coupled with enhanced heat exchangers, significantly reduces operating costs and energy bills, aligning with today’s sustainability goals.

The PKG-PRC002-EN features a robust and durable construction, which translates to enhanced longevity and reduced maintenance requirements. Designed for ease of installation, the unit is compact and lightweight, facilitating seamless retrofitting and integration into existing systems. Furthermore, its accessible service panels allow for straightforward maintenance and repairs, thus minimizing downtime and service disruptions.

Equipped with Trane's advanced control technology, the PKG-PRC002-EN offers precise temperature management, ensuring consistent comfort across different zones within a building. The intuitive controls enable users to program schedules and adjust settings based on their specific needs, enhancing comfort while maximizing efficiency.

The model also incorporates advanced filtration options, improving indoor air quality by effectively reducing pollutants and allergens. This focus on health and safety is essential, especially in commercial settings where air quality can significantly impact occupant well-being and productivity.

Another notable characteristic of the PKG-PRC002-EN is its low noise levels during operation, which is essential for maintaining a conducive indoor environment in workplaces, retail spaces, or educational institutions. The unit's design minimizes sound transmission, creating a more pleasant atmosphere for occupants.

In summary, the Trane PKG-PRC002-EN is a highly efficient, reliable, and user-friendly rooftop unit that combines advanced technology with robust construction. Its energy-saving features, superior air quality options, and focus on quiet performance make it an excellent choice for modern commercial HVAC applications, ultimately contributing to sustainable building practices and enhanced occupant comfort.