Performance

Water-Cooled

Data

46 Ton

 

 

 

 

Table PD-26. SCWF/SIWF 46 - Economizer Full Capacity - 18,400 cfm

Entering WaterTemp

Entering Air

 

 

45 F

 

 

55 F

 

EDB

EWB

Flow

Total

Sensible

LWT

Total

Sensible

LWT

F

F

gpm

MBh

MBh

F

MBh

MBh

F

 

 

115

469.0

425.0

53.2

295.0

295.0

60.1

 

62

138

488.5

433.3

52.1

302.5

302.5

59.4

 

 

142

491.5

434.5

51.9

303.5

303.5

59.3

 

 

115

594.6

360.1

55.3

344.7

266.9

61.0

75

67

138

630.9

374.4

54.1

362.5

273.2

60.3

 

 

142

636.3

376.6

54.0

365.3

274.2

60.1

 

 

115

760.7

300.9

58.2

493.5

207.5

63.6

 

72

138

808.6

318.4

56.7

526.8

218.7

62.6

 

 

142

815.8

321.1

56.5

531.8

220.3

62.5

 

 

115

515.3

504.7

54.0

368.6

368.6

61.4

 

62

138

530.5

519.8

52.7

377.9

377.9

60.5

 

 

142

532.7

522.0

52.5

379.2

379.2

60.3

 

 

115

605.5

459.2

55.5

380.0

374.4

61.6

80

67

138

637.2

471.8

54.2

393.5

379.2

60.7

 

 

142

642.0

473.7

54.0

395.6

380.0

60.6

 

 

115

759.0

396.1

58.2

493.9

303.3

63.6

 

72

138

806.6

413.9

56.7

525.5

313.9

62.6

 

 

142

813.8

416.6

56.5

530.3

315.5

62.5

 

 

115

586.3

586.3

55.2

442.1

442.1

62.7

 

62

138

601.2

601.2

53.7

453.1

453.1

61.6

 

 

142

603.4

603.4

53.5

454.7

454.7

61.4

 

 

115

631.8

564.1

56.0

443.5

443.5

62.7

85

67

138

658.8

574.9

54.5

454.6

454.6

61.6

 

 

142

662.8

576.6

54.3

456.2

456.2

61.4

 

 

115

761.0

492.1

58.2

511.5

404.5

63.9

 

72

138

806.5

509.1

56.7

538.2

413.4

62.8

 

 

142

813.3

511.6

56.5

542.2

414.8

62.6

Table PD-27. SCWF/SIWF 46 - Economizer Low Capacity - 18,400 cfm

Entering Water Temp

Entering Air

 

 

45 F

 

 

55 F

 

EDB

EWB

Water Flow

Total

Sensible

LWT

Total

Sensible

LWT

F

F

gpm

MBh

MBh

F

MBh

MBh

F

 

 

115

309.1

298.4

50.4

203.6

203.6

58.5

 

62

138

321.0

315.6

49.7

209.4

209.4

58.0

 

 

142

322.8

316.3

49.5

210.3

210.3

58.0

 

 

115

390.9

254.1

51.8

224.1

194.0

58.9

75

67

138

413.0

262.5

51.0

234.6

197.6

58.4

 

 

142

416.4

263.8

50.9

236.3

198.2

58.3

 

 

115

499.2

201.2

53.7

324.1

142.3

60.6

 

72

138

528.4

211.6

52.7

343.5

148.6

60.0

 

 

142

532.8

213.1

52.5

346.4

149.6

59.9

 

 

115

353.2

353.2

51.1

254.4

254.4

59.4

 

62

138

363.6

363.6

50.3

261.7

261.7

58.8

 

 

142

365.1

365.1

50.1

262.8

262.8

58.7

 

 

115

394.0

330.3

51.9

255.0

243.6

59.4

80

67

138

413.9

337.9

51.0

262.9

251.4

58.8

 

 

142

417.0

339.1

50.9

264.1

252.5

58.7

 

 

115

498.1

276.3

53.7

323.0

217.5

60.6

 

72

138

527.3

286.6

52.6

342.3

223.7

60.0

 

 

142

531.6

288.1

52.5

345.2

224.7

59.9

 

 

115

403.6

403.6

52.0

305.3

305.3

60.3

 

62

138

415.5

415.5

51.0

314.0

314.0

59.6

 

 

142

417.2

417.2

50.9

315.3

315.3

59.4

 

 

115

414.9

413.1

52.2

305.9

305.9

60.3

85

67

138

431.2

419.4

51.2

314.6

314.6

59.6

 

 

142

433.7

420.3

51.1

315.9

315.9

59.4

 

 

115

497.1

351.2

53.6

331.7

295.6

60.8

 

72

138

526.1

361.4

52.6

347.6

300.7

60.0

 

 

142

530.5

363.0

52.5

350.0

301.5

59.9

48

PKG-PRC002-EN

Page 48
Image 48
Trane PKG-PRC002-EN manual 46 Ton, Table PD-27. SCWF/SIWF 46 Economizer Low Capacity 18,400 cfm

PKG-PRC002-EN specifications

The Trane PKG-PRC002-EN is a groundbreaking packaged rooftop unit designed to meet the diverse needs of commercial and industrial spaces. This model showcases Trane’s commitment to innovation, energy efficiency, and reliability, making it a preferred choice for HVAC professionals and building owners alike.

One of the main features of the PKG-PRC002-EN is its high-efficiency design. This unit leverages advanced technologies to minimize energy consumption while ensuring optimal cooling and heating performance. Its efficient compressor, coupled with enhanced heat exchangers, significantly reduces operating costs and energy bills, aligning with today’s sustainability goals.

The PKG-PRC002-EN features a robust and durable construction, which translates to enhanced longevity and reduced maintenance requirements. Designed for ease of installation, the unit is compact and lightweight, facilitating seamless retrofitting and integration into existing systems. Furthermore, its accessible service panels allow for straightforward maintenance and repairs, thus minimizing downtime and service disruptions.

Equipped with Trane's advanced control technology, the PKG-PRC002-EN offers precise temperature management, ensuring consistent comfort across different zones within a building. The intuitive controls enable users to program schedules and adjust settings based on their specific needs, enhancing comfort while maximizing efficiency.

The model also incorporates advanced filtration options, improving indoor air quality by effectively reducing pollutants and allergens. This focus on health and safety is essential, especially in commercial settings where air quality can significantly impact occupant well-being and productivity.

Another notable characteristic of the PKG-PRC002-EN is its low noise levels during operation, which is essential for maintaining a conducive indoor environment in workplaces, retail spaces, or educational institutions. The unit's design minimizes sound transmission, creating a more pleasant atmosphere for occupants.

In summary, the Trane PKG-PRC002-EN is a highly efficient, reliable, and user-friendly rooftop unit that combines advanced technology with robust construction. Its energy-saving features, superior air quality options, and focus on quiet performance make it an excellent choice for modern commercial HVAC applications, ultimately contributing to sustainable building practices and enhanced occupant comfort.