Trane PKG-PRC002-EN manual 25 Ton, Table PD-9. SCWF/SIWF 25 Economizer Low Capacity 10,000 cfm

Models: PKG-PRC002-EN

1 101
Download 101 pages 31.23 Kb
Page 36
Image 36

Performance

Water-Cooled

Data

25 Ton

 

 

 

 

Table PD-8. SCWF/SIWF 25 - Economizer Full Capacity -10,000 cfm

 

 

 

 

 

Entering Water Temp

 

 

Entering Air

 

 

45 F

 

 

55 F

 

EDB

EWB

Flow

Total

Sensible

LWT

Total

Sensible

LWT

F

F

gpm

MBh

MBh

F

MBh

MBh

F

 

 

63

250.7

229.6

53.0

159.0

159.0

60.0

 

62

75

261.4

234.1

52.0

163.2

163.2

59.4

 

 

80

265.2

235.7

51.6

164.6

164.6

59.1

 

 

63

316.1

193.1

55.0

183.8

144.0

60.8

75

67

75

335.6

200.8

53.9

193.5

147.5

60.2

 

 

80

342.5

203.6

53.6

197.0

148.7

59.9

 

 

63

404.1

160.2

57.8

262.3

110.9

63.3

 

72

75

429.9

169.5

56.5

280.2

116.9

62.5

 

 

80

439.1

172.9

56.0

286.5

119.0

62.2

 

 

63

276.9

271.1

53.8

198.7

198.7

61.3

 

62

75

285.3

279.5

52.6

203.9

203.9

60.4

 

 

80

288.2

282.4

52.2

205.6

205.6

60.1

 

 

63

322.6

247.4

55.2

203.9

202.9

61.5

80

67

75

339.8

254.2

54.1

211.3

205.6

60.6

 

 

80

345.9

256.6

53.6

213.9

206.5

60.3

 

 

63

403.2

212.1

57.8

262.8

163.2

63.3

 

72

75

428.9

221.6

56.4

279.7

168.8

62.5

 

 

80

438.1

225.0

56.0

285.8

170.9

62.1

 

 

63

315.6

315.6

55.0

238.3

238.3

62.6

 

62

75

324.1

324.1

53.6

244.6

244.6

61.5

 

 

80

326.9

326.9

53.2

246.6

246.6

61.2

 

 

63

337.7

304.9

55.7

239.1

239.1

62.6

85

67

75

352.4

310.7

54.4

245.3

245.3

61.5

 

 

80

357.6

312.8

53.9

247.4

247.4

61.2

 

 

63

404.8

264.6

57.9

273.0

218.6

63.7

 

72

75

429.2

273.6

56.4

287.4

223.4

62.7

 

 

80

438.0

276.9

55.9

292.5

225.1

62.3

 

 

 

 

 

 

 

 

 

Table PD-9. SCWF/SIWF 25 - Economizer Low Capacity - 10,000 cfm

 

 

 

 

 

Entering Water Temp

 

 

Entering Air

 

 

45 F

 

 

55 F

 

EDB

EWB

Flow

Total

Sensible

LWT

Total

Sensible

LWT

F

F

gpm

MBh

MBh

F

MBh

MBh

F

 

 

63

164.5

158.7

50.2

109.2

109.2

58.5

 

62

75

171.1

170.9

49.6

112.6

112.6

58.0

 

 

80

173.5

171.9

49.3

113.7

113.7

57.8

 

 

63

205.7

136.0

51.5

118.7

104.8

58.8

75

67

75

218.1

140.7

50.8

124.5

106.8

58.3

 

 

80

222.4

142.3

50.6

126.7

107.6

58.2

 

 

63

262.5

106.4

53.3

170.7

75.8

60.4

 

72

75

278.7

112.1

52.4

181.4

79.2

59.8

 

 

80

284.5

114.1

52.1

185.2

80.4

59.6

 

 

63

189.1

189.1

51.0

136.5

136.5

59.3

 

62

75

195.2

195.2

50.2

140.7

140.7

58.8

 

 

80

197.2

197.2

49.9

142.2

142.2

58.6

 

 

63

208.1

178.0

51.6

136.8

136.8

59.3

80

67

75

219.1

182.2

50.8

141.1

134.8

58.8

 

 

80

223.1

183.7

50.6

142.6

136.4

58.6

 

 

63

262.0

147.5

53.3

170.2

116.9

60.4

 

72

75

278.1

153.2

52.4

180.8

120.4

59.8

 

 

80

283.9

155.2

52.1

184.6

121.6

59.6

 

 

63

216.2

216.2

51.9

163.9

163.9

60.2

 

62

75

223.0

223.0

50.9

168.9

168.9

59.5

 

 

80

225.4

225.4

50.6

170.6

170.6

59.3

 

 

63

220.7

214.1

52.0

164.2

164.2

60.2

85

67

75

229.7

227.2

51.1

169.2

169.2

59.5

 

 

80

233.0

228.4

50.8

170.9

170.9

59.3

 

 

63

261.5

188.6

53.3

175.9

160.0

60.6

 

72

75

277.6

194.2

52.4

184.5

162.8

59.9

 

 

80

283.2

196.2

52.1

187.7

163.8

59.7

36

PKG-PRC002-EN

Page 36
Image 36
Trane PKG-PRC002-EN manual 25 Ton, Table PD-9. SCWF/SIWF 25 Economizer Low Capacity 10,000 cfm