Trane PKG-PRC002-EN manual 94.5

Models: PKG-PRC002-EN

1 101
Download 101 pages 31.23 Kb
Page 41
Image 41

Performance

Water-Cooled

Data

32 Ton

 

 

 

 

 

 

Table PD-16. SCWF/SIWF 32 Gross Cooling Capacity - 12,800 cfm, 96 gpm

Entering Water Temp

Entering Air

 

75 F

 

 

85 F

 

 

95 F

 

EDB

EWB

Total

Sensible

 

Total

Sensible

 

Total

Sensible

 

F

F

MBh

MBh

LWT

MBh

MBh

LWT

MBh

MBh

LWT

 

62

367

317

83.9

352

310

93.8

337

303

103.7

75

67

398

246

84.6

382

240

94.5

365

233

104.3

 

72

432

175

85.3

415

169

95.2

397

163

105.0

 

62

374

372

84.1

361

360

94.0

348

348

103.9

80

67

398

313

84.6

382

307

94.5

365

300

104.3

 

72

431

241

85.3

415

236

95.2

397

229

105.0

 

62

393

393

84.5

380

380

94.4

367

367

104.3

85

67

401

377

84.7

386

370

94.6

369

361

104.4

 

72

431

308

85.3

414

302

95.2

395

296

105.0

Chart PD-35. SCWF/SIWF 32 Fan Performance for CV or with VFD

Chart PD-36. SCWF/SIWF 32 Fan Performance with Inlet GuideVanes

Note:

1.Fan curves include refrigerant coil and internal cabinet static losses.To determine static pressure to be used with these curves, add filter, economizer, flexible horizontal discharge and heat pressure drops to external duct static pressure.

PKG-PRC002-EN

41

Page 41
Image 41
Trane PKG-PRC002-EN manual 94.5