Trane PKGP-PRC001-EN Performance, Data12½ - 20Tons, Table PD-20- Auxiliary Electric Heat Capacity

Models: PKGP-PRC001-EN

1 52
Download 52 pages 53.39 Kb
Page 25
Image 25
Table PD-19— Heating Capacity Correction Factors

Performance

Data(12½ - 20Tons)

Table PD-19— Heating Capacity Correction Factors

% Variation of Nominal CFM

- 20

- 10

0

+ 10

+ 20

Total Gross Capacity Multiplier

.96

.98

1.0

1.01

1.02

 

 

 

 

 

 

Table PD-20 — Auxiliary Electric Heat Capacity

 

 

Total2

 

 

 

Stage 1

 

 

 

 

Stage 2

 

 

Unit

KW

MBh

 

No. of

KW

MBh

 

KW

MBh

Tons

Model No.

Input1

Output1

 

Stages

Input1

Output1

Input1

Output1

 

 

18.00

 

61.00

1

18.00

61.00

 

 

12½, 15

WC*150B3, B4, BW

36.00

 

123.00

2

18.00

61.00

 

18.00

61.00

 

 

WC*180B3, B4, BW

54.00

 

184.00

2

36.00

123.00

 

18.00

61.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36.00

 

123.00

2

18.00

61.00

 

18.00

61.00

 

20

WC* 240B3, B4, BW

54.00

 

184.00

2

36.00

123.00

 

18.00

61.00

 

 

 

72.00

 

246.00

2

36.00

123.00

 

36.00

123.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Does not include indoor fan power or heat.

 

 

Voltage

 

 

 

 

 

 

 

 

 

2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =(

 

 

)2 x rated cap.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RatedVoltage

Table PD-21 —Electric Heater Voltage

Correction Factors (Applicable to Auxiliary

Heat Capacity)

 

 

 

 

 

Nominal

 

 

Distribution

 

Capacity

 

 

 

 

 

Voltage

 

 

Voltage

 

Multiplier

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208

 

0.75

 

 

 

 

240

 

 

 

 

 

230

 

0.92

 

 

 

 

 

 

 

 

 

 

 

240

 

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

440

 

0.84

 

 

 

 

480

 

 

 

 

 

460

 

0.94

 

 

 

 

 

 

 

 

 

 

 

480

 

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

540

 

0.81

 

 

 

 

600

 

 

 

 

 

575

 

0.92

 

 

 

 

 

 

 

 

 

 

 

600

 

1.00

 

 

 

 

 

 

 

 

 

 

Table PD-22— Air Temperature Rise Across Electric Heaters (Degree F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12½ Ton

 

 

 

 

15Ton

 

20Ton

 

 

 

 

5000 CFM

 

 

6000 CFM

 

 

8000 CFM

 

 

 

 

Three Phase

 

 

Three Phase

 

Three Phase

 

KW

Stages

 

WC*150B

 

 

WC*180B

 

WC*240B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.00

1

 

 

 

 

 

 

 

 

 

 

17.30

1

 

 

 

 

 

 

 

 

 

 

18.00

1

 

11.4

 

 

 

 

9.5

 

 

 

 

27.00

2

 

 

 

 

 

 

 

 

 

 

36.00

2

 

23.0

 

 

 

 

19.0

 

 

 

 

14.2

54.00

2

 

34.1

 

 

 

 

28.4

 

 

 

 

21.3

72.00

2

 

 

 

 

 

 

 

 

 

 

28.5

 

 

 

 

 

 

 

 

 

 

Table PD-23 — Electric Heater Temperature Rise Correction Factors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

% Variation From Nominal CFM

- 20

- 15

- 10

- 5

0

 

+5

+10

+15

+20

 

 

 

 

 

 

 

 

 

 

Temperature Rise Multiplier

1.25

1.17

1.11

1.05

1.00

0.95

0.91

0.87

0.83

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Indicates both downflow and horizontal units.

PKGP-PRC001-EN

25