Trane PKGP-PRC001-EN manual Performance, Data15Ton, 61.6

Models: PKGP-PRC001-EN

1 52
Download 52 pages 53.39 Kb
Page 23
Image 23
61.6

Performance

Data(15Ton)

Table PD-16 — 15 Ton Downflow Three Phase Heating Capacities (Net) WC*180B3, B4, BW at 6000 CFM

Outdoor

Integrated Heating Capacity (MBh/1000)

Total Power in Kilowatts At

At Indicated Indoor Dry Bulb Temp.

Indicated Indoor Dry Bulb Temp.

Temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F.

60

70

75

80

 

60

70

75

80

 

 

 

 

 

 

 

 

 

 

 

 

-8

61.6

60.4

59.9

59.6

 

11.35

12.19

12.67

13.20

 

-3

67.6

66.4

65.9

65.5

 

11.55

12.39

12.88

13.41

 

2

74.0

72.8

72.3

71.9

 

11.74

12.62

13.12

13.65

 

7

80.8

79.6

79.1

78.6

 

11.94

12.84

13.34

13.88

 

12

88.0

86.8

86.2

85.7

 

12.15

13.06

13.57

14.12

 

17

95.8

94.3

93.7

93.2

 

12.36

13.29

13.81

14.37

 

22

104.1

102.5

101.8

101.1

 

12.59

13.54

14.07

14.63

 

27

113.0

111.2

110.3

109.6

 

12.84

13.80

14.33

14.91

 

32

122.3

120.3

119.3

118.4

 

13.10

14.07

14.61

15.20

 

37

131.6

129.8

128.3

127.3

 

13.36

14.35

14.90

15.50

 

42

141.3

138.8

137.6

136.5

 

13.63

14.64

15.20

15.81

 

47

172.0

168.8

167.3

165.8

 

14.97

16.07

16.68

17.34

 

52

183.8

180.3

178.6

177.1

 

15.31

16.42

17.05

17.71

 

57

196.1

192.2

190.4

188.6

 

15.66

16.80

17.43

18.10

 

62

208.6

204.3

202.3

200.3

 

16.04

17.19

17.83

18.51

 

67

217.8

212.8

210.4

208.0

 

16.35

17.50

18.13

18.80

 

72

230.9

225.6

222.9

220.4

 

16.79

17.95

18.59

19.27

 

For other airflow conditions, see heating capacity correction factor (Table PD-19).

Net Heating Capacity and Power Input include indoor fan heat at nominal cfm and .35 inch ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.

Heating capacities and powers are integrated to include the effects of defrost in the frost region. All heating capacities and power (kW) are at 70% OD relative humidity.

PKGP-PRC001-EN

23

Page 23
Image 23
Trane PKGP-PRC001-EN manual Performance, Data15Ton, 61.6