Electrical
Data
Table
|
|
|
|
|
| Compressor Motors |
|
|
| Condenser Fan Motors |
|
| |||||
| Unit |
|
|
|
|
|
| Amps1 |
|
|
|
|
|
| Amps1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Tons | Model No. | No. | Volts | Phase | HP2 | RPM |
| RLA | LRA | No. | Phase | HP | FLA | LRA | |||
| WC*150B3 | 2 | 3 | 6.00 | 3450 | 21.7 | 156 | 2 | 1 | .50 | 3.2 | 8.8 | |||||
12½ | WC*150B4 | 2 | 460 | 3 | 6.00 | 3450 | 10.0 | 75 | 2 | 1 | .50 | 1.6 | 4.0 | ||||
| WC*150BW | 2 | 575 | 3 | 6.00 | 3450 | 8.2 | 54 | 2 | 1 | .50 | 1.3 | 3.2 | ||||
| WC*180B3 | 2 | 3 | 5.70/9.00 | 3450/3500 | 30.1/20.4 | 225/156 | 2 | 1 | .50 | 3.2 | 8.8 | |||||
15 | WC*180B4 | 2 | 460 | 3 | 5.70/9.00 | 3450/3500 | 15.6/10.8 | 114/75 | 2 | 1 | .50 | 1.6 | 4.0 | ||||
| WC*180BW | 2 | 575 | 3 | 5.70/9.00 | 3450/3500 | 12.1/8.5 | 80/54 | 2 | 1 | .50 | 1.3 | 3.2 | ||||
| WC*240B3 | 2 | 3 | 9.00 | 3500 | 30.1 | 225 | 2 | 1 | 1.00 | 5.5 | 18.3 | |||||
20 | WC*240B4 | 2 | 460 | 3 | 9.00 | 3500 | 15.8 | 114 | 2 | 1 | 1.00 | 2.9 | 9.3 | ||||
| WC*240BW | 2 | 575 | 3 | 9.00 | 3500 | 12.2 | 80 | 2 | 1 | 1.00 | 2.0 | 5.7 |
Notes:
1Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2.HP for each compressor.
*Indicates both downflow and horizontal units.
32 |