Trane PKGP-PRC001-EN manual Electrical Data, Volts Three Phase

Models: PKGP-PRC001-EN

1 52
Download 52 pages 53.39 Kb
Page 29
Image 29
460 Volts Three Phase

Electrical

Data

Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection, Continued)

 

 

 

 

 

 

StandardIndoorMotor

 

Oversize Indoor Motor

 

 

To Use

Heater

Heater

Control

 

 

Max Fuse Size or

 

Max Fuse Size or

Tons

With

Model No.

KW Rating1

Stages

 

MCA

Max Circuit Breaker2

MCA

Max Circuit Breaker2

 

 

 

460 Volts Three Phase

 

 

 

 

 

 

 

AYDHTRK418A

18.0

1

58

60

 

61

70

 

 

WCD150B4

AYDHTRK436A

36.0

2

85

90

 

88

90

 

 

 

AYDHTRK454A

54.0

2

112

125

 

115

125

 

12½

 

AYHHTRP418A

18.0

1

58

60

 

61

70

 

 

 

 

 

 

WCH150B4

AYHHTRP436A

36.0

2

85

90

 

88

90

 

 

 

AYHHTRP454A

54.0

2

112

125

 

115

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AYDHTRK418A

18.0

1

66

70

 

69

70

 

 

WCD180B4

AYDHTRK436A

36.0

2

93

100

 

96

100

 

 

 

AYDHTRK454A

54.0

2

120

125

 

123

125

 

15

 

AYHHTRP418A

18.0

1

66

70

 

69

70

 

 

 

 

 

 

WCH180B4

AYHHTRP436A

36.0

2

93

100

 

96

100

 

 

 

AYHHTRP454A

54.0

2

120

125

 

123

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AYDHTRL436A

36.0

2

104

110

 

107

110

 

 

WCD240B4

AYDHTRL454A

54.0

2

131

150

 

134

150

 

 

 

AYDHTRK472A

72.0

2

158

175

 

161

175

 

20

 

AYHHTRN436A

36.0

2

104

110

 

107

110

 

 

 

 

 

 

WCH240B4

AYHHTRN454A

54.0

2

131

150

 

134

150

 

 

 

AYHHTRN472A

72.0

2

158

175

 

161

175

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

1.Heater kw ratings are at 480V for 460V unit

2.HACR type circuit breaker per NEC.

PKGP-PRC001-EN

29

Page 29
Image 29