Economizer with

Performance

Data(12½ - 20Tons)

Table PD-13 — Static Pressure Drops Through Accessories (Inches Water Column)

 

 

 

 

 

Economizer with

 

 

 

Electric Heater

 

 

 

 

 

 

 

 

OA/RA Dampers1

 

 

 

Accessory (kW)2

 

 

Unit

 

Standard

2 Inch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tons

Model No.

CFM

Filters3

Pleated Filters4

100% OA

100% RA

5-12

14-23

36

54

 

72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4000

0.05

0.08

0.20

0.02

0.03

0.03

0.04

12½

WC*150B

5000

0.07

0.11

0.26

0.03

0.04

0.05

0.06

 

 

6000

0.11

0.15

0.35

0.04

0.06

0.07

0.09

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4800

0.07

0.10

0.24

0.03

0.04

0.04

0.05

15

WC*180B

6000

0.11

0.15

0.35

0.04

0.06

0.07

0.08

 

 

7200

0.15

0.19

0.42

0.05

0.09

0.10

0.12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6400

0.07

0.11

0.22

0.04

0.06

0.08

0.09

 

WCD240B

8000

0.11

0.15

0.31

0.05

0.10

0.12

0.14

 

 

9600

0.16

0.02

0.44

0.07

0.14

0.17

0.20

20

 

6400

0.06

0.01

0.22

0.04

0.06

0.08

0.09

 

WCH240B

8000

0.09

0.13

0.31

0.05

0.10

0.12

0.14

 

 

9600

0.13

0.17

0.44

0.07

0.14

0.17

0.20

Notes:

1.OA = Outside Air and RA = Return Air.

2.Nominal KW ratings at 240, 480, 600 volts.

3.Tested with:2" filters 12½-20 tons.

4.Difference in pressure drop should be considered when utilizing optional 2” pleated filters.

*Indicates both downflow and horizontal units.

PKGP-PRC001-EN

21