Electrical
Data
Table
|
|
|
|
|
| StandardIndoorMotor |
| Oversize Indoor Motor |
| ||
| To Use | Heater | Heater | Control |
|
| Max Fuse Size or |
| Max Fuse Size or | ||
Tons | With | Model No. | KW Rating1 | Stages |
| MCA | Max Circuit Breaker2 | MCA | Max Circuit Breaker2 | ||
|
|
| 208/230 Volts Three Phase |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| AYDHTRK318A | 13.5/18.0 | 1 | 113/120 | 125/125 |
| 119/127 | 125/150 |
| |
| WCD150B3 | AYDHTRK336A | 27.0/36.0 | 2 | 160/175 | 175/175 |
| 166/181 | 175/200 |
| |
|
| AYDHTRK354A | 40.5/54.0 | 2 | 207/229 | 225/250 |
| 213/235 | 225/250 |
| |
12½ |
| AYHHTRN318A | 13.5/18.0 | 1 | 113/120 | 125/125 |
| 119/127 | 125/150 |
| |
|
|
|
| ||||||||
| WCH150B3 | AYHHTRP336A | 27.0/36.0 | 2 | 160/175 | 175/175 |
| 166/181 | 175/200 |
| |
|
| AYHHTRP354A | 40.5/54.0 | 2 | 207/229 | 225/250 |
| 213/235 | 225/250 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| AYDHTRK318A | 13.5/18.0 | 1 | 122/130 | 125/150 |
| 129/136 | 150/150 |
| |
| WCD180B3 | AYDHTRK336A | 27.0/36.0 | 2 | 169/184 | 175/200 |
| 175/190 | 175/200 |
| |
|
| AYDHTRK354A | 40.5/54.0 | 2 | 216/238 | 225/250 |
| 222/244 | 225/250 |
| |
15 |
| AYHHTRN318A | 13.5/18.0 | 1 | 122/130 | 125/150 |
| 129/136 | 150/150 |
| |
|
|
|
| ||||||||
| WCH180B3 | AYHHTRP336A | 27.0/36.0 | 2 | 169/184 | 175/200 |
| 175/190 | 175/200 |
| |
|
| AYHHTRP354A | 40.5/54.0 | 2 | 216/238 | 225/250 |
| 222/244 | 225/250 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| AYDHTRL336A | 27.0/36.0 | 2 | 190/204 | 200/225 |
| 197/212 | 200/225 |
| |
| WCD240B3 | AYDHTRL354A | 40.5/54.0 | 2 | 237/258 | 250/300 |
| 244/266 | 250/300 |
| |
|
| AYDHTRK372A | 54.0/72.0 | 2 | 284/312 | 300/350 |
| 291/320 | 300/350 |
| |
20 |
| AYHHTRN336A | 27.0/36.0 | 2 | 190/204 | 200/225 |
| 197/212 | 200/225 |
| |
|
|
|
| ||||||||
| WCH240B3 | AYHHTRN354A | 40.5/54.0 | 2 | 237/258 | 250/300 |
| 177/266 | 250/300 |
| |
|
| AYHHTRN372A | 54.0/72.0 | 2 | 284/312 | 300/350 |
| 224/320 | 300/350 |
|
Notes:
1.Heater kw ratings are at 208/240 for 208/230V unit 480V for 460 V unit
2.HACR type circuit breaker per NEC.
*Indicates both downflow and horizontal units.
28 |