Trane TCONT802AS32DA, TCONT803AS32DA System Checkout, Installer System Test

Models: TCONT803AS32DA TCONT802AS32DA

1 20
Download 20 pages 51.81 Kb
Page 17
Image 17

TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION

SYSTEM CHECKOUT

Installer System Test

The Installer System Test mode is used to test the HVAC system(s). See Table 5. While in System Test mode, minimum off-time for compressors is bypassed.

The Installer Test is part of the Installer Setup options. Enter Installer Setup screen and press the Down arrow key to bring up test selection(s) quickly.

SYSTEM CHECKOUT CAUTION

Equipment Damage Hazard.

Minimum compressor off-time is bypassed during Installer System Test.

Avoid cycling compressor quickly.

Table 5. System Test(s).

 

 

 

 

 

 

 

 

Installer

Factory Setting

 

Other Choices

 

Select

Setup

 

 

 

 

 

Number

Options

Description

Options

Description

Comments

 

 

 

 

 

 

 

Installer

Test 1

0

Cool is off

1,2

0—cool off

System selection

Test Cool

 

 

 

 

1—cool stage 1 turns on

determines which

 

 

 

 

 

2—cool stages 1 and 2 on

tests are available

 

 

 

 

 

 

and the number of

 

 

 

 

 

 

stages shown.

 

 

 

 

 

 

 

Installer

Test 2

0

Fan is off

1

0—fan off

Test Fan

 

 

 

 

1—fan turns on

 

 

 

 

 

 

 

 

Installer

Test 3

0

Heat is off

1-3

0—heat off

Test Heat

 

 

 

 

1—stage 1 heat on

 

 

 

 

 

 

2—stages 1 and 2 heat on

 

 

 

 

 

 

3—stages 1, 2 and 3 (Aux

 

 

 

 

 

 

Ht) on

 

 

 

 

 

 

 

 

Installer

Test 4

0

Emergency

1

0—emergency heat off

Available only if

Test Em

 

 

heat is off

 

1—emergency heat on

heat pump with

Ht

 

 

 

 

2—emergency heat and

auxiliary heat is

 

 

 

 

 

auxiliary heat turn on

selected.

 

 

 

 

 

 

 

 

Pub. No. 18-HD25D19-3

17

69-1790—3

Page 17
Image 17
Trane TCONT802AS32DA, TCONT803AS32DA installation instructions System Checkout, Installer System Test