TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Table 4. Installer Setup Menu. (Continued)
|
|
|
|
|
|
|
|
| Factory Setting |
| Other Choices |
| |
| Installer |
|
|
|
|
|
Select | Setup |
|
|
|
|
|
Number | Option | Description | Options | Description | Comments | |
Deadband | 0310 | 2 thru 9 | Heating and cooling | 3 | Heating and cooling setpoints | Shown only if |
|
|
| setpoints can be set |
| can be set no closer than 3°F | automatic |
|
|
| no closer than chosen |
| (1.5°C). | changeover is |
|
|
| value: |
|
| selected. |
|
|
|
|
| The deadband is | |
|
|
|
|
| restricted to the range | |
|
|
|
|
| of 5 to 9 if ISU 0380 is | |
|
|
|
|
| set to | |
|
|
|
|
| dehumidification | |
|
|
|
|
| droop control. | |
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
|
|
|
|
Temperature | 0320 | 0 | Temperature is | 1 | Temperature is displayed in °C. | — |
Indication |
|
| displayed in °F. |
|
|
|
Scale |
|
|
|
|
|
|
Daylight | 0330 | 1 | Daylight savings | 0, 2 | Set to 0 in areas that | |
Savings |
|
| enabled (use through |
| disabled. | do not follow daylight |
|
|
| 2006 and for areas |
| savings. | |
|
|
| that do not use the |
| (start using in 2007, for areas |
|
|
|
| new 2007 DST |
| that use the new 2007 DST |
|
|
|
| calendar). |
| calendar). |
|
Remote | 0340 | 0 | No remote | Defaults and Options | ||
Temperature |
|
| temperature sensor |
| sensor for display only. | depend on System |
Sensor |
|
|
|
| Type selection. | |
(Outdoor or |
|
|
|
| sensor for system control, | Indoor Temperature |
Indoor) |
|
|
|
| used for select heat pump | Sensor uses an |
|
|
|
|
| systems. (See Special Heat | averaging network |
|
|
|
|
| Pump Features section for | and does not include |
|
|
|
|
| more details.) | |
|
|
|
|
|
| |
Heat Pump | 0350 | 0 | No compressor | 15, 20, | 15°F | Default depends on |
Compressor |
|
| lockout. | 25, 30, | 20°F | other selections. |
Lockout |
|
|
| 35, 40, | 25°F | Shown if Outdoor |
|
|
|
| 45 | 30°F | Temperature for |
|
|
|
|
| 35°F (1.5°C) | control is selected. |
|
|
|
|
| 40°F (4.5°C) |
|
|
|
|
|
| 45°F (7°C) |
|
|
|
|
|
|
|
|
Heat Pump | 0360 | 0 | No heat pump | 40, 45, | 40°F (4.5°C) | Shown if electric is |
Auxiliary |
|
| auxiliary lockout. | 50, 55, | 45°F (7°C) | chosen for backup |
Lockout |
|
|
| 60 | 50°F (10°C) | heat source and |
|
|
|
|
| 55°F (13°C) | outdoor temperature |
|
|
|
|
| 60°F (15.5°C | sensor for control is |
|
|
|
|
|
| selected. |
Indoor | 0380 | 0 | No indoor | 1 | Available on models | |
Dehumidifica- |
|
| dehumidification |
| control. | with humidity sensor. |
tion Control |
|
| control. |
|
|
|
Furnace Filter | 0500 | 0 | Furnace filter change | Run time based on | ||
Change |
|
| reminder off. |
| call for fan. | |
Reminder |
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
|
|
| |
Humidifier | 0510 | 0 | Humidifier pad | — | ||
Pad |
|
| replacement reminder |
|
| |
Replacement |
|
| off. |
|
| |
Reminder |
|
|
|
|
|
|
Pub. No. |
|
14 |