Powering the Comfort Control

TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION

 

 

 

 

 

HEAT PUMP

 

 

 

 

 

Y2

 

 

 

1

 

RC

 

 

 

F

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

X2

 

 

 

 

 

O

 

 

 

W1

 

 

 

 

 

Y

 

 

2

S1

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

T

S2

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VARIABLE

R

BK

O

G

YLO

Y

W1

W2

B/C

SPEED

TWO STAGE

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

FURNACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR

 

 

 

 

 

 

 

 

 

OUTDOOR

 

 

 

R

Y2

Y1

O

X2/BK

BR(T)

 

B

16 SEER

 

HEAT PUMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O.D. SECTION

 

 

 

 

 

 

 

 

 

(TWO STEP)

 

 

 

 

 

 

 

 

 

 

 

TO POWER SUPPLY

 

(3 PH

 

 

1

FACTORY INSTALLED JUMPER.

PER LOCAL CODES

 

ONLY)

 

 

 

 

 

 

 

2

OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CABLE SEPARATE FROM THE THERMOSTAT CABLE.

 

 

 

 

 

 

 

 

 

 

 

 

 

3

REMOVE / CUT JUMPER FROM R TO BK.

 

M24203

 

 

 

 

 

 

 

 

Fig. 15. Typical hookup of multistage two-step scroll heat pump with two stage variable speed gas furnace

(3H/2C heat pump).

Powering the Comfort Control

The Comfort Control can be powered with 24 Vac.

24 Vac Common Power (Recommended)

Wire the common side of the transformer to the B screw of the comfort control wallplate. When installing in a single transformer system, keep the jumper wire between the R and Rc screws. When installing in a two-transformer system, use the common from the cooling transformer to connect to the B screw and remove the jumper wire between the R and Rc screws.

Battery Power (Optional)

24 Vac Common Power (Recommended) CAUTION

Equipment or Property Damage Hazard. Using battery power only may not provide adequate power to comfort control and can cause damage during freezing conditions. Connect the 24 Vac Common (B) wire from the system transformer to the comfort control for proper operation when the battery power is drained.

Three AAA alkaline batteries can be used to power the comfort control for armchair programming only. To prevent the comfort control and heating/cooling system from shutting down due to lack of battery power, it is not recommended that the comfort control be solely powered with the three AAA batteries during normal system operation. When using batteries, make sure positive and negative terminals are oriented correctly, as marked on the device. See Fig. 16.

BATTERIES (3)

M19918

Fig. 16. Installing batteries on comfort control back.