Trane TRG-TRC007-EN manual Air Handler Test Configurations, Equipment Sound Rating, period four

Models: TRG-TRC007-EN

1 82
Download 82 pages 1.27 Kb
Page 66
Image 66
Air Handler Test Configurations

period four

Equipment Sound Rating

notes

Air Handler Test Configurations

ducted

ducted

discharge

inlet

 

casing

unducted inlet

plus casing

radiated

radiated

 

Figure 64

In order to isolate these different paths, the air handler must be tested using a number of different configurations. For example, to determine the portion of the sound that is discharged with the air into the supply ductwork, the air handler is installed outside of the reverberant room with the supply air ducted into the room.

In order to determine the sound that travels back down the return duct in a ducted inlet application, the air handler is again installed outside of the reverberant room, but the return air duct is connected to the reverberant room.

In order to determine the portion of the sound that is radiated by the casing, the air handler is installed inside the reverberant room with both the return and supply air ducted outside of the room.

Finally, in cases where the return air travels back to the air handler through an open plenum and into the open equipment room, the combined “free” (or open) inlet plus casing radiated sound level must be known. Therefore, the air handler is installed inside the reverberant room with a free inlet and the supply air is ducted to outside of the room.

TRG-TRC007-EN

59

Page 66
Image 66
Trane TRG-TRC007-EN manual Air Handler Test Configurations, Equipment Sound Rating, period four