VII.
VII. p - ADJUSTING THE ROOM TEMPERATURE OFFSET:
The room temperature offset parameter allows a service technician or end user the ability to have the display show a temperature that is within three degrees of the actual temperature being read by the cabinet air sensor. This allows for continuity of reading between different temperature reading devices. (i.e.: thermistor Vs thermocouple Vs handheld thermometer) This parameter is preset at the factory to “0” or no offset.
Follow the instructions to enter the customer access code on page 9. When the control displays
Thermostat Set High, press the down arrow keyuntil the control display reads
Room Temperature Offset. Press the set button SET . Use the arrow keys to adjust the offset to your desired setting. When the display shows the offset you want press the set button SET .
The display will then read Thermostat Set Point High. You can use the up or down arrow
keys | to scroll to the next parameter or press the alarm cancel button to exit | ) . |
|
| )) |
VII. q - SETTING THE AUDIBLE ALARM STYLE:
This parameter will allow the customer to turn on/off the audible alarm feature on the INTELA- TRAUL® control. The audible alarm is preset from the factory to OFF. The customer can choose between an audible alarm that sounds for 3 seconds then automatically turns off, or a continuous audible alarm that must be manually acknowledged. Regardless of this feature’s setting, visual alarm text will display when conditions warrant.
To adjust this setting, follow the instructions to enter the customer access code on page 9. When the
control displays |
|
|
|
|
|
| Thermostat Set Point High, press the up arrow key |
| until the display | ||||||||||||||||||||||||||
|
|
|
|
|
|
| |||||||||||||||||||||||||||||
|
|
|
|
|
|
| |||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SET . The display will read |
|
|
|
|
|
|
|
| ||
reads |
|
|
|
|
|
|
| Audible Alarm Style. Press the set button |
|
|
|
|
|
|
| OFF. | |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||||||
|
|
|
|
|
|
| |||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Use the arrow keys |
|
|
|
|
| to scroll between |
|
|
|
|
|
| for the | ||||||||||||||||||||||
|
|
| |||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
| |||||||||||||||||||||||||||
|
| ||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
for Continuous Audible Alarm. When the display shows your choice of style, press the set
button SET . The display will then read thermostat Set Point High. Use the arrow keys
|
|
| )) |
|
|
| |
to scroll to the next parameter or press the Alarm Cancel Button |
|
| ) to exit. |