Convection Circuit
8-10
Blower Motor Controller Fault Codes & Troubleshooting
NOTE: If no fault condition exists, the LED wi ll be green. If a fault condition exists, the LED will flas h
redhen a local keypad is not connected. All faults c an be reset by cycling the reset control input,
pressing the stop key, or cycling power, except as noted in the Corrective Action c olumn below.
NOTE: To recycle power, disconnect power for a full minute, or until the LED ex tinguishes, before
reapplying power.
Reliance Blower Motor Controller Fault Codes & Troubleshooting
# of
LED
Flashes
Fault
Description
Fault Cause
Corrective Action
2 Control Input Illegal control input sequence 3–wir e: Verify Start and Jog inputs
are not both ON
2–wire: Verify that only one input
(Forward, Reverse, or Jog) is ON
2 Function Loss Start attempt while STOP
(function loss) input is off Verify STOP (function loss) input
is ON before attempting to start
drive.
3 Under Voltage Low input line
Temporary loss of input line
Check input line to verify voltage is
within operating specifications
4 Over Voltage High input line
Decel time too fast
Overhauling load
Check input line to verify voltage is
within operating specifications
Increase decel time
5 Drive Overload Excessive driven load Reduc e the load
5 Motor Overload Excessive driven load Verif y P-02 is set correctly
Reduce the load.
Check for mechanical binding
6 Over Temperature
Operating environment is too hot
�� Fan is blocked or not operating
Excessive driven load
Verify the ambient temperature is
<50ºC
Verify clearance above/below
drive
Check for fan obstruction. Replace
if necessary
Reduce the carrier frequency (P–
64)
Reduce the load
7 Over Current
(300%) Shaft rotation blocked
Excessive driven load
Output wiring is incorrect or
shorted
Check for obstructions to shaft
rotation or reduce excessive load
Increase accel/decel time
Verify output wiring is correct
8 Bad Keypad
Connection Bad connection from keypad to
drive Verify keypad is properly
connected to drive