MX4428 MXP Engineering / Technical Manual

Document: LT0273

Analog Loop Design Considerations

 

4.1 ANALOGUE LOOP CONFIGURATION SELECTION

4.1.1LINES & LOOPS

The interface between the MXP and its addressable devices requires two wires.

The MXP has two lines (“left” and “right”) which are designed to be connected in a loop.

The LOOP configuration is generally preferred and indeed will often be mandatory for compliance with standards as discussed below.

However the MXP can be used to connect to multiple lines in a star configuration. Dual line mode is not supported.

4.1.2LOOP FAULT TOLERANCE

Standards require that a line/loop fault condition cause minimal disruption to the system's ability to detect and transmit alarms to the Fire Panel. The MXP achieves this in the following way .....

The MXP has access to each device from both ends of the loop. The loop is normally sourced from “left” and monitored at the “right” terminals. Disappearance of 40V power at the “right” end, due to an open circuit FAULT on either the + or – wires, can be detected (causing a FAULT event to be sent to the MX4428 Master) and corrected by switching the Line driver onto the “right” terminals. The LOOP mode is therefore inherently fault tolerant to any one open circuit on any one of the 2 wires.

However, a short circuit on the loop will, in general, cause the MXP to loose communication with all devices. Thus it is recommended that isolator bases be used to minimise the loss due to a short.

When designing fire alarm systems, the designer should be aware of any local statutory requirements, as well as those of AS1670.1 and NZS4512.

4.1.3AS1670.1 DESIGN REQUIREMENTS

Australian Standard AS1670.1 sections 3.1 and 3.2 require the analogue loop to comply with the following:

The maximum number of actuating devices (i.e. detectors and input modules) in an alarm zone shall not exceed 40.

A single short circuit shall not disable more than 40 devices connected to the MXP loop/line. This means than if more than 40 devices are to be connected to an MXP, short circuit isolators must be used. The count of 40 includes conventional detectors connected to a DIM800 or other ancillary input device

4.1.4NZS4512 DESIGN REQUIREMENTS

Isolator Bases must be fitted between zones (or on the first device either side of a zone boundary) so that a single short circuit or break will affect no more than one zone.

In many cases the tones produced by the 814SB sounder base are not acceptable. Refer to NZS4512 for detailed requirements.

Page 4-2

24 March 2006

Issue 1.5

Page 70
Image 70
Tyco MX4428 Analogue Loop Configuration Selection, Lines & Loops, Loop Fault Tolerance, 3 AS1670.1 Design Requirements

MX4428 specifications

The Tyco MX4428 is a cutting-edge device known for its robust performance in the realm of wireless communication and sensor acquisition. Tailored for applications in various sectors, the MX4428 is particularly well-suited for industrial automation, environmental monitoring, and smart city initiatives. With its advanced features, the device has gained tremendous popularity among engineers and developers looking for reliability and efficiency in data transmission.

One of the standout features of the MX4428 is its exceptional range, which can extend up to several kilometers under optimal conditions. This long-range capability ensures that data can be transmitted over vast distances without degradation in quality, making it ideal for remote monitoring applications. Additionally, the device operates on multiple frequency bands, providing flexibility in deployment based on specific regional requirements and regulatory guidelines.

The MX4428 utilizes a highly efficient radio protocol that enhances data throughput while reducing power consumption. This asymmetric data transmission method allows for low-duty cycle operation, extending battery life and autonomy. The device's energy efficiency is particularly beneficial in applications where frequent battery replacement would be impractical, such as in environmental sensors and agricultural monitoring systems.

Furthermore, the MX4428 is equipped with comprehensive sensor integration capabilities. It can seamlessly interface with various sensors, making it a versatile choice for collecting a wide range of data types. From temperature and humidity sensors to motion detectors, the MX4428 can serve as a central hub for data gathering and transmission, providing real-time insights into environmental conditions.

Security is also a paramount consideration in the design of the MX4428. It incorporates robust encryption and authentication protocols to safeguard data integrity during transmission. This feature is crucial for applications involving sensitive information or those that require compliance with strict regulatory frameworks.

In summary, the Tyco MX4428 is a powerful and versatile device that boasts a combination of long-range communication, low power consumption, and comprehensive sensor integration capabilities. Its robust security features further enhance its appeal for critical applications across various industries. Whether for industrial, environmental, or smart city use cases, the MX4428 stands out as a reliable solution that meets the demands of modern wireless communication landscapes.