MX4428 MXP Engineering / Technical Manual

Document: LT0273

Device Information and Programming

 

 

 

 

3.6

MX4428 PROGRAMMING

 

In the following sections information is given about the programming of each device in the MX4428. An explanation of the mode and the various parameters is given for each device type, along with the global parameters that affect that device type. It is critical that only the listed mode values are used for each device type, as in many cases the mode value is used to define the actual device type. An incorrect mode value may cause a POINT TYPE MISMATCH to be generated, or it may just render a device not able to work.

In some of the following sections descriptions are given about changing the sensitivity for a detector by altering the specific parameter for that detector. This is correct (it sets the value for just that individual detector), but in many cases it may be better to adjust the global sensitivity for that device type so that all detectors of that type take on the new value. For example, in NZ mode it is recommended that the global heat alarm temperature be set to 57°C for both 814PH and 814CH, rather than setting each specific detector to this value.

Details for NZ mode settings are contained in the F4000 NZ Technical Manual (LT0126).

These details are most relevant when programming the MX4428 from a (dumb) programming terminal. Alternatively you can program with "SmartConfig", which displays and edits functional parameters and takes care of mapping the functional parameters into the appropriate mode and parameter bytes for each device type.

Page 3-14

24 March 2006

Issue 1.5