MX4428 MXP Engineering / Technical Manual

 

Device Information and Programming

 

 

3.8

814I IONISATION SMOKE DETECTOR

3.8.1GENERAL

The 814I is an ionisation smoke detector. The detector senses the amount of smoke present and sends this value to the MXP. The MXP makes any decisions as to whether this is an alarm, fault, normal or whatever. The integral LED is turned on by the MXP when an alarm is detected.

The remote LED and functional base outputs are programmable for their functionality (refer to section 3.3).

3.8.2814I SPECIFICATIONS

Line Connections

L(–), L1(+)

Supply Voltage

20Vdc - 40Vdc

Supply Current

330uA (typical quiescent)

Alarm Current

3.0mA (typical)

Remote LED Current

7mA (Tyco E500Mk2)

Dimensions

110mm (diameter) x 55mm (including MUB base)

Weight

81g

Base

MUB, 5B, 5BI, 814RB, 814SB, or MkII Sounder Base

3.8.3MX4428 PROGRAMMING OPTIONS - 814I

The programmable values for the 814I are explained in the following table.

Normally only the mode needs to be programmed, and then only if a functional base or remote LED is required and its operation is different from the default. Refer to section 3.3.

In some cases the alarm sensitivity (Parameter 1) may need to be changed from the default. The approved range for Australia is 0.22 MIC X (23) to 0.39 MIC X ( 66). The available range is 0.22 MIC X (23) to 0.59 MIC X (130). If the alarm sensitivity is changed, the pre-alarm sensitivity (Parameter 0) should normally be changed to about 75% of the alarm sensitivity.

The remaining parameters should not need changing.

Issue 1.5

24 March 2006

Page 3-17