Tyco MX4428 technical manual Point Allocation For Various Numbers of Logical Responders, Nlr

Models: MX4428

1 134
Download 134 pages 47.81 Kb
Page 14
Image 14

MX4428 MXP Engineering / Technical Manual

 

Document: LT0273

Responder Loop Design Considerations

 

 

 

 

 

 

 

 

 

 

Number of Logical

Number of Circuits (Relays)

Number of Points per circuit

Total Quantity of Points

 

 

Responders

available

(relay)

in Last Circuit

 

 

(NLR)

(NC = 4 * NLR)

PC = 200/NC

 

 

 

 

 

 

 

 

 

1

4

50

50

 

 

2

8

25

25

 

 

3

12

16

24

 

 

4

16

12

20

 

 

5

20

10

10

 

 

6

24

8

16

 

 

7

28

7

11

 

 

8

32

6

14

 

 

9

36

5

25

 

 

10

40

5

5

 

 

11

44

4

28

 

 

12

48

4

12

 

 

13

52

3

47

 

 

14

56

3

35

 

 

15

60

3

23

 

 

16

64

3

11

 

 

17

68

2

66

 

 

18

72

2

58

 

 

19

76

2

50

 

 

20

80

2

42

 

 

21

84

2

34

 

 

22

88

2

26

 

 

23

92

2

18

 

 

24

96

2

10

 

 

25

100

2

2

 

 

26

104

1

97

 

 

27

108

1

93

 

 

28

112

1

89

 

 

29

116

1

85

 

 

30

120

1

81

 

 

31

124

1

77

 

 

32

128

1

73

 

 

33

132

1

69

 

 

34

136

1

65

 

 

35

140

1

61

 

 

36

144

1

57

 

 

37

148

1

53

 

 

38

152

1

49

 

 

39

156

1

45

 

 

40

160

1

41

 

 

41

164

1

37

 

 

42

168

1

33

 

 

43

172

1

29

 

 

44

176

1

25

 

 

45

180

1

21

 

 

46

184

1

17

 

 

47

188

1

13

 

 

48

192

1

9

 

 

49

196

1

5

 

 

50

200

1

1

 

 

 

 

 

 

 

Table 2-1 Point Allocation For Various Numbers of Logical Responders

Page 2-4

24 March 2006

Issue 1.5

Page 14
Image 14
Tyco MX4428 technical manual Point Allocation For Various Numbers of Logical Responders, Nlr