MX4428 MXP Engineering / Technical Manual

Document: LT0273

Device Information and Programming

 

All loop devices are rated at a loop voltage of 20Vdc - 40Vdc and a signalling voltage of 2V p-p – 6V p-p. Alarm Currents specified do not include remote indicators. Add 7mA for each remote indicator.

DEVICE

FUNCTION

Comments

 

 

 

 

 

814I

 

Ionisation Smoke Detector

Requires base

814H

 

Heat Detector

Requires base

814PH

Photo Smoke + Heat

Requires base

Detector

 

 

 

 

 

814P

 

Photo Smoke Detector

Requires base

814CH

CO + Heat Detector

Requires base

MIM800

Mini Input Module

EOL 200Ω

 

Alarm R (if used) 100Ω

 

 

 

 

Max Wiring R 10Ω

 

 

 

Mini Input Module

N/O mode - as MIM800

MIM801

(normally closed interrupt)

N/C -

 

EOL 200Ω

 

 

 

 

 

 

 

 

Max wiring R 50Ω

CIM800

Contact Input Module

EOL 200Ω

 

Alarm R (if used) 100Ω

 

 

 

 

Max Wiring R 10Ω

DIM800

(Conventional) Detector

EOL 4k7

Interface Monitor

Requires separate supply.

 

 

 

CP820

Call Point

 

FP0838, FP0839

NZ Call Point

 

RIM800

Relay Interface Module

2A 30Vdc

 

 

 

Sounder Notification

2A 30Vdc.

SNM800

Module (Supervised relay

Requires external supply.

 

 

 

output)

 

LPS800

Loop Powered Sounder

Provides 24V at up to 75mA

Module

 

 

 

 

 

MUB

 

Standard Base

 

5BI

 

Isolator Base

 

814SB

Loop Powered Sounder

Selectable tone (not AS2220 or ISO8201)

Base

Adjustable sound level

 

 

 

 

 

 

Loop Powered Sounder

Selectable tone (Including AS2220 and ISO

 

 

802SB

Base

8201 Evacuation tone)

 

 

 

 

Adjustable sound level

 

 

812SB

Loop Powered Sounder

Selectable tone (Including AS2220 and ISO

MkII

 

Base

8201 Evacuation tone)

 

 

 

 

Externally Powered

Selectable tone (Including AS2220 and ISO

Sounder

 

 

 

 

Sounder Base

8201 Evacuation tone)

Bases

 

901SB

 

 

Adjustable Sound Level.

 

 

 

 

 

 

 

 

Requires external 24V

 

 

 

Externally Powered

Selectable tone (Including AS2220 and ISO

 

 

912SB

Sounder Base

8201 Evacuation tone)

 

 

 

 

Requires external 24V

814RB

Relay Base

1A 30Vdc

 

2 pole changeover

 

 

 

 

VLC800

Vesda aspirating smoke

Requires external supply. Requires PC to

detector

set up.

 

 

 

 

 

 

 

 

Table 3-1 Compatible Device Summary

The MXP will allow some alternative devices to be used without generating a fault, where the inserted device can provide all the features of the configured device. This includes an 814PH or 814CH used where an 814H was programmed, a CIM800 used where a MIM800 was programmed, and an 814PH used where an 814P was programmed.

Page 3-6

24 March 2006

Issue 1.5

Page 22
Image 22