Configuring Optional and Recommended UPS

Configuring Optional and Recommended UPS

The Uninterruptible Power Supply (UPS) option enables the system to gracefully shut down in the event of a power interruption on the main supply line. The available styles are listed in Table 6–35. If the site UPS does not provide power and status to the entire system (CEC, APC, etc), it should provide power and status connections for the SCP’s and all servers. See Figure 6–11 for single SCP/server to UPS status cable connection/site UPS installation. See Figure 6–12 for dual SCP/servers to UPS status cable connection/site UPS installation. If a UPS jumper cable is not listed for the installed UPS model, make a cable as follows:

 

UPS Specific

 

9-Pin

 

D-Connector

 

Connector

 

(Male)

 

 

 

 

Battery Low

 

 

 

 

1

 

 

 

 

 

 

 

 

Signal N.O.

 

 

 

2

Contact

 

 

 

3

Ground

 

 

 

4

 

 

 

 

5

 

 

 

 

 

 

 

 

6

AC Fail

 

 

 

7

 

 

 

 

8

 

 

 

 

Signal N.O.

 

 

 

9

Contact

 

 

 

0232

 

 

 

 

Please note that style UPS111-EXP should be ordered for each additional NT server. It contains one distribution box and the proper jumper cable to connect to the NT server.

When a central site UPS is used for a dual domain system with redundant SCP consoles, style CBL5-UPS must be ordered separately to cable SCPA and SCPB. See Figure 6–12.

Table 6–35. UPS Options

Component

Interconnect Configuration and

Industry-Compatible UPS Systems

Notes

Style Name

Cable Part No.

 

 

 

 

 

 

 

UPS Jumper Cables

 

 

 

 

 

UPS915-WC1

15-Pin Male “D” to 9-Pin Male

Deltec PowerWorks

1, 2, 7

 

(7015 5411-000)

 

 

UPS99-WC2

9-Pin Male “D” to 9-Pin Male

American Power Conversion and Phase One

1, 2, 7

 

(7015 6260-000)

UPS and Deltec 1000i

 

UPS925-WC3

25-Pin Male “D” to 9-Pin Male

Best Power Tech

1, 2, 7

 

(7015 6278-000)

 

 

UPS925-WC4

25-Pin Male “D” to 9-Pin Male

Exide Powerware and Powerware Plus

1, 2, 7

 

(7015 5429-000)

 

 

UPS99-WC5

9-Pin Male “D” to 9-Pin Male

Deltec 2000

1, 2, 7

 

(7015 6260-002)

 

 

6–50

7017 6300–005

Page 156
Image 156
Unisys NX5820 manual Configuring Optional and Recommended UPS, UPS Options