Vermont Casting 3399, 3369 Vertical Termination - Direct Vent ONLY, Vent Termination Clearances

Models: 3369 3390 3399 3360 3225 3354 3350 3232

1 44
Download 44 pages 26.46 Kb
Page 8
Image 8
Vertical Termination - Direct Vent ONLY

Radiance Direct Vent/Natural Vent Gas Heater

Vertical Termination - Direct Vent ONLY

A vertical vent system must terminate no less than 8’ (2.44m) and no more than 40’ (12m) above the appli- ance flue collar. A 2¹⁄" restrictor plate (supplied) must be used, where specified, in all vertically terminated vent systems. (Refer to Figure 8) NOTE: The restrictor plate supplied with the vertical termination should be discarded. Install restrictor plate supplied with stove directly at stove outlet. A vertically terminated vent system must also conform to the following criteria:

No more than three 90° elbows may be used.

Two 45° elbows may be substituted for one 90˚ elbow. No more than six 45° elbows may be used.

Vent must rise a minimum of 2 feet before offset is used.

Termination height must conform to roof clearance as specified in Figure 9.

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All

Vertical

 

Termi

-

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nations in

this area

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

pipe.)

 

 

Require use of

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

the 2¹⁄” Restrictor

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

vent

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Plate*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

top

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to the

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

collar

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

feet)(in flue

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vertical terminations

 

 

 

 

 

 

 

 

 

Run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

must be within this area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

appliance

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vertical the

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Measure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unacceptable

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

Venting

Configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

���

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

���

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No offset

may be

used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

within

this area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

� � � � � � � � � �� �� �� �� �� �� �� �� ��

�� ��

 

 

 

 

 

 

 

 

Horizontal Run (in feet)

 

ST132a

Fig. 8 Vertical vent termination window.

*The Restictor Plate is used on Direct Vent installations only.

Vent Termination Clearances

When planning the installation, consider the location of the vent terminal and clearances. Some of the most common clearances to keep in mind are shown in Figure 9.

Important: All vent clearances must be maintained. Check your vent termination clearances against Figures 9 through 11.

The vent should be placed so that people cannot be burned by accidentally touching the vent surfaces when the stove is operating.

The vent termination should be located where it cannot be damaged by such things as automobile doors, lawn mowers or snowblowers and it should be located away from areas where it could become blocked by snow, etc.

Some considerations are:

Obstructions or impediments to venting.

Nearby combustible materials that could come into contact with combustion exhaust gases.

Other nearby openings {within 12” (305 mm)} through which exhaust gas could reenter the build- ing.

All vegetation within 3’ (76 mm) that may interfere with the draft.

Other factors that influence where the installation will be sited include the location of outside walls, where additional heat may be desired in the home, where the family members gather most regularly, and perhaps most importantly, the distance limitations of the venting system.

IMPORTANT

Direct Vent Only

The horizontal termination must not be recessed into the exterior wall or siding.

Horizontal vent runs must be level toward the vent termination.

Clearances around the vent termination must be maintained.

For installations using Simpson DuraVent pipe, parallel installations with minimum wall clearance have restricted access for connecting the Hori- zontal Vent Cap straps to the vent pipe. See the maker’s instructions for recommended installa- tion procedures.