Radiance Direct Vent/Natural Vent Gas Heater

CAUTION

This appliance should only be connected by a qualified gas technician. Test to confirm manifold pressures as specified below.

The Radiance Heater and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).

The Radiance Heater must be isolated from the gas supply piping system by closing its indi- vidual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 psig.

There must be a gas shutoff between the stove and the supply.

In order to connect Natural Gas, use a fitting with 1/2” NPT on the valve side and 1/2” natural gas supply line with an input of 35,000 BTUs at a manifold pressure of 3.5” between minimum inlet supply of 5.5” w.c. and maximum of 14.0” w.c.

In order to connect Propane, use a fitting with 1/2” NPT on the valve side and 1/2” propane gas sup- ply line with an input of 35,000 BTUs at a manifold pressure of 10.0” between a minimum inlet supply of 11.0” w.c. and maximum of 14.0” w.c.

Burner Information

The appliance must only use the gas specified on the rating plate, unless converted using a Vermont Castings Fuel Conversion Kit. To convert from LP to Natural Gas use Kit #000-5009. To convert from Natural Gas to LP use Kit #000-5010.

Conversion instructions are provided with each kit and beginning on Page 29 in this manual.

THIS APPLIANCE SHOULD BE CON- NECTED TO THE GAS SUPPLY ONLY BY A QUALIFIED GAS SERVICE TECHNICIAN. FOLLOW ALL LOCAL CODES.

THERE MUST BE A GAS SHUT-OFF BE- TWEEN THE STOVE AND THE SUPPLY.

In order to connect Natural Gas, use a fitting with 1/2” NPT on the valve side and 1/2” natural gas supply line with an input of 35,000 BTUs at a manifold pressure of 3.5” between minimum inlet supply of 5.5” w.c. and maximum of 14.0” w.c.

In order to connect Propane, use a fitting with 1/2” NPT on the valve side and 1/2” propane gas supply line with an input of 35,000 BTUs at a manifold pressure of 10.0” between a minimum inlet supply of 11.0” w.c. and maximum of 14.0” w.c.

Install ON/OFF Switch

The switch assembly parts are found in the parts bag.

1.Attach switch assembly to left rear side of stove shroud (when facing shroud) using two screws and existing holes in shroud. (Fig. 42)

2.Run wires down back of stove, under bottom of rear shroud to valve.

3.Attach wires to valve terminals. (Fig. 43)

Switch As-

semblyExisting Holes

Screws

ST315

 

Fig. 42 Attach switch assembly to rear shroud.

TPTH TP TH

PILOT

ADJ

ST228

Fig. 43 Attach switch wires to valve.

Thermostat Connection (optional)

Use only a thermostat rated for 500 - 750 millivolts.

Check the table below for the appropriate gauge ther- mostat wire to use for the length of lead required in your installation.

Thermostat

 

Wire / Gauge

Maximum Run

18

20 feet

16

20 - 40 feet

14

up to 60 feet

1.Install the wall thermostat in the desired location and run the wires to the stove location. Terminate these leads with 1/4” female connectors.

2.Connect the thermostat wires to the valve. (Fig. 43)

Install the Mesh and Grille

Place the mesh and grille on the top of the Radiance stove to complete assembly.

2222

20004188

Page 22
Image 22
Vermont Casting 3350, 3399, 3369, 3354, 3232, 3225 Burner Information, Install ON/OFF Switch, Thermostat Connection optional