LDVR Series Direct Vent Gas Fireplace
Troubleshooting - Honeywell Millivolt Valve
| Remove Window Frame Assembly Before Service Work |
START | CHECK |
Gas Supply On
YES
▼
Pilot Lights With Piezo Ignitor
YES
▼
Pilot Stays Lit
YES
▼
Pilot Lights Main Burner
YES
| NO | ▼ | • Supply Line Hooked Up | ||
| • | Shutoff Valve Open | |||
|
|
| |||
|
|
|
|
| |
|
|
|
|
| |
|
|
| • Lockout Has Engaged. Wait 60 |
| |
|
|
|
| Seconds And Try Again. |
|
|
| ▼ | • For Spark At Electrode While |
| |
| NO |
| Depressing Piezo |
| |
|
|
|
| ||
|
|
| 1/8" Gap To Pilot Hood Needed. |
| |
|
|
|
|
| |
|
|
| • | All Wiring Connections |
|
|
|
| • | Replace Piezo Ignitor |
|
|
|
|
|
| |
|
|
|
|
| |
|
|
| • For Air In The Lines |
| |
|
|
| • Thermopile Needs A Min. |
| |
|
|
|
| 325mv. Adjust Pilot Flame |
|
|
|
|
| Height. |
|
| NO | ▼ | • | All Wiring Connections |
|
| • | Replace Thermopile |
| ||
|
|
| • Thermocouple Needs A Min. Of |
| |
|
|
|
| 14mv |
|
|
|
| • Defective Valve. Turn To Pilot, |
| |
|
|
|
| Meter Should Read Greater |
|
|
|
|
| Than 100mv. If Not, Replace. |
|
|
|
|
|
| |
|
|
|
|
| |
|
|
| • Valve Is Turned On |
| |
|
|
| • Wall Switch Is Not Turned On. |
| |
| NO | ▼ |
| Watch For Grounded Wires! |
|
|
|
| • Thermopile Needs A Min. 325mv. |
| |
|
|
| • | Plugged Burner Orifice |
|
|
|
|
|
|
|
▼
SYSTEM OK
10007317 | 29 |