Vermont Casting BHDR36 installation instructions Vertical Through The Roof Applications

Models: BHDR36

1 36
Download 36 pages 8.11 Kb
Page 24
Image 24
VERTICAL THROUGH THE

DO NOT BACK FILL AROUND SNORKEL. SOIL SHOULD NOT BE LESS THAN 4" BELOW SNORKEL.

c) A minimum of an 8 ft. vertical rise.

d) Two sets of 45 degree elbow offsets within these

vertical installations. From 0 to a maximum of 8 ft. a

vent pipe can be used between elbows. (Fig. 59)

e) 7DVCS must be used to support offsets. (Fig. 60)

This application will require that you first determine the roof

pitch and use the appropriate 7TDVSKV (A,B or F). (see

FOUNDATION

RECESS

WATERTIGHT

SEAL

AROUND

PIPE

SNORKEL

WALL

SCREWS

Venting Components, page 27)

SHEET METAL

 

SCREWS

Fig. 57

 

Fig. 59

MAX. 8 Ft.

)

If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to wall first and then secure to snorkel with self drilling #8 x 1/2 sheet metal screws. It will be necessary to extend vent pipes out as far protruding wall face (Fig. 57).

VERTICAL THROUGH THE

ROOF APPLICATIONS

MAXIMUM

10 FT

(3048mm)

MINIMUM

8 FT./

MAXIMUM

40 FT.

VERTICAL

RISE

 

(2438mm)

 

MAX.

MAX. 8 Ft.

40 FEET

(2438mm)

(12.2m)

 

MIN.

 

8 FEET

 

(2.44m)

SIDE VIEW

 

TYPICAL 7DVCS

APPLICATION

TYPICAL ROOF

SUPPORT

APPLICATION

Fig. 60

Fig. 61

PIPE STRAPS

EVERY 3'

(914mm)

Fig. 58

This Gas Fireplace has been approved for,

a)Vertical installations up to 40 feet (12 metres) in height. Up to a 10 ft. horizontal vent run can be installed within the vent system using a maximum of three 90o elbows.

b)Up to two 45o elbows may be used within the horizontal run. For each 45o elbow used on the horizontal level the maximum horizontal length must be reduced by 18 inches.

Example: Maximum horizontal length

 

0

-

45o elbows

10 ft.

1

-

45o elbows

8.5 ft.

2

-

45o elbows

7 ft.

VENT TERMINATION

 

 

STORM COLLAR

ROOF

24" Min.

ROOF FLASHING

 

 

(610mm)

 

 

 

ROOF SUPPORT

ATTIC INSULATION

 

 

JOISTS

CEILING JOISTS

40 FEET

 

 

 

(12.2m)

 

 

 

ATTIC INSULATION

 

 

SHIELD

 

Fig. 62

TYPICAL STRAIGHT-UP INSTALLATION

The minimum height of the vent above the highest point of penetration throught the roof is 2 feet. See Fig. 62.

- 24 -

Page 24
Image 24
Vermont Casting BHDR36 installation instructions Vertical Through The Roof Applications