Troubleshooting – Honeywell VS8421

DVRT41 Direct Vent Gas Fireplace

Troubleshooting – Honeywell VS8421

Window Frame Assembly to be Removed Before Service Work

START

Gas Supply On

NO

CHECK

Supply Line Hooked Up

Shutoff Valve Open

YES

Pilot Lights With Piezo Ignitor

YES

PILOT STAYS LIT

YES

PILOT LIGHTS MAIN BURNER

YES

SYSTEM OK

 

 

 

 

 

Lockout Has Engaged. Wait 60

 

 

 

 

 

 

Seconds And Try Again.

 

 

 

 

For Spark At Electrode While

 

NO

 

 

Depressing Piezo

 

 

 

 

 

 

 

 

 

1/8" Gap To Pilot Hood Needed.

 

 

 

 

 

 

 

 

 

 

All Wiring Connections

 

 

 

 

 

Replace Piezo Ignitor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For Air In The Lines

 

 

 

 

 

Thermopile Needs A Min.

 

 

 

 

 

 

325mv. Adjust Pilot Flame

 

 

 

 

 

 

Height.

 

 

 

All Wiring Connections

 

NO

 

 

 

Replace Thermopile

 

 

 

 

 

Thermocouple Needs A Min. Of

 

 

 

 

 

 

14mv

 

 

 

 

 

 

 

 

 

Valve Is Turned On

 

 

Wall Switch Is Not Turned On.

 

 

Watch For Grounded Wires!

NO

 

 

Thermopile Needs A Min. 325mv.

 

 

 

 

 

 

Plugged Burner Orifice

 

 

Defective Valve. Turn To Pilot,

 

 

 

Meter Should Read Greater Than

 

 

 

100mv. If Not, Replace.

 

 

 

 