VISTA-10SE Installation and Setup Guide
A-2
UL NOTICES1. This is a "Grade A" residential system.
2. The 4285/4286 VIP Module and 7720PLUS or 7820 Long-Range Radios have no t been UL
tested and cannot, therefore, be used in a UL installation.
3. The Entry Delay (field ✱38) cannot be greater than 45 seconds for UL installations.
4. The maximum number of reports per armed period (field ✱92) must be unlimited (set to 1)
for UL installations.
5. Periodic testing (field ✱49) must be at least every 24 hours ( set to 1) for UL installations.
6. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL
installations.
7. Downloading is not permissible for UL installations unless an in staller is present at the
installation site.
CALIFORNIA STATE FIRE MARSHAL (CSFM) AND UL RESIDENTIAL FIRE24 HOUR BATTERY BACKUP REQUIREMENTSThe California State Fire Marshal and UL have regulations that require all residential fire alarm control
panels to be provided with a backup battery that has sufficien t capacity to operate the panel and its
attached peripheral devices for 24 hours in the intended standby co ndition , follo wed by at least 4 minutes
in the intended fire alarm signaling condition.
This control panel can meet these requirements without using a supplementary power supply, provided
that the panel's auxiliary power and bell output currents are limited as indicated below .
OUTPUT LIMITATIONS TO MEET CSFM 24 HOUR BATTERY BACKUP REQUIREMENTS AND UL LISTED
RESIDENTIAL FIRE INSTALLATIONS
OUTPUT CURRENT LIMITATIONS BATTERY INFORMATION
OUTPUT CURRENT
TOTAL MAXIMUM
AUXILIARY CURRENT BATTERY CAPACITY
TO USE (Amp/Hrs)
RECOMMENDED
BATTERY
(Yuasa Model No.)
600mA maximum total
of
auxiliary power
plus bell output
currents
45mA
160mA
200mA
425mA
500mA
4AH
7AH
8AH
14AH
17.2AH
NP4-12
NP7-12
NP4-12 (two)‡
NP7-12 (two)‡
NPG18-12
‡NOTE: Use two batteries, connected in parallel. Obtain an ADEMCO Battery Harness ki t. A dual-battery
harness is provided with the kit. Both batteries will fit inside the panel's cabinet.