INSTALLATION
8)Install optional Remote Control, or Wall Ther- mostat, page 13.
9)Final check, page 14.
Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly and operation fully explained to cus- tomer.
This includes:
1)Clocking the appliance to ensure the cor- rect firing rate (rate noted on label) after burning appliance for 15 minutes.
2)If required, adjusting the primary air to ensure that the flame does not carbon. First allow the unit to burn for
CAUTION: Any alteration to the product that causes sooting or carboning or that results in damage is not the responsibil- ity of the manufacturer.
CLEARANCES TO COMBUSTIBLES
The clearances listed below are MINIMUM dis- tances. Measure the clearance to both the appliance and the chimney connector. (The farthest distance is correct if the two clearances do not coincide.) For example, if the appliance is set as indicated in one of the figures but the connector is too close, move the stove until the correct clearance to the connec- tor is obtained.
be in the down position when control panel is in place.
4) Push black knob onto speed control.
5) Remove the rear access panel on the back of the stove. Remove the 3 top screws, but only loosen the 3 bottom screws - the panel can then be lifted off. Install the fan onto pins as per diagram 2.
This unit can be installed on a solid combustible surface like a wood floor. This unit can also be installed directly on carpeting or vinyl when the bottom pedestal cover plate (provided with unit) is installed.
| Diagram 2 | |
OPTIONAL FAN | ||
Hint for pushing fan down onto pins - rub | ||
INSTALLATION | a bit of dish soap on the pins so the | |
grommets will slide down more easily. | ||
| Check to make sure the fan is seated | |
Fan Kit Contains: | properly on the pins - try to move the fan | |
| back and forth. |
This appliance may be installed only with the clearances as shown in the situations pictured. Do not combine clearances from one type of installation with another in order to achieve closer clearances.
Use the minimum clearances shown in the diagrams below for installation with "B" vent.
E63-NG1 & E63-LP1 Clearances
A Left Side Wall to Unit | 6" | / 150 mm |
B Right Side Wall to Unit | 10" | / 255 mm |
C Back Wall to Unit | 5" | / 125 mm |
D Vertical Vent Pipe to |
|
|
Back Wall | 2" | / 50 mm |
E Unit Corner to Wall | 2" | / 50 mm |
Qty. Description
1Fan Speed Controller with nut, and knob.
1Fan Assembly c/w green wire attached
1power cord
1Plastic locking grommet
1)Remove the Top Control Panel Assembly by removing the three screws. Diagram 1.
6)Push power cord through hole in the rear panel 14" - 16" and tie a loose knot in the cord on the inside to prevent the power cord from being pulled out. Diagram 2.
7)Install locking grommet to power cord and push through hole in the rear panel and give a 1/4 turn to secure.
NOTE: When running wires, keep them clear of valve assembly and tubing to avoid tangling of wires and valve.
NOTE: Be careful not to cut wires when passing through holes in the fire- box.
Mantel | 18" | / 460 mm |
|
| 8) Run green ground wire from fan and con- |
|
| nect to grounding lug. | |||
Unit to Alcove Ceiling | 18" | / 460 mm |
|
| |
|
|
| |||
Max. Alcove Depth | 24" | / 610 mm |
| Diagram 1 |
|
|
|
|
|
| |
Minimum ceiling height is 18" / 460 mm from top | 2) Remove the nylon hole plug from the con- |
| |||
of unit. |
|
|
| ||
|
|
| trol panel. |
| |
|
|
|
|
| |
If further reduced clearances are needed, | 3) | Install the fan speed controller onto the |
| ||
obtain requirements for construction of a pro- |
| ||||
| control panel and secure with nut. Connect |
| |||
tected wall from your local building authorities |
|
| |||
| remaining wire harness wires to speed |
| |||
and their allowable reductions | of the listed |
|
| ||
| control. NOTE: Speed control wires must |
| |||
clearances. |
|
|
|
| |
|
|
|
|
| |
Waterford | 7 |