INSTALLATION
GAS CONNECTION
The gas line can be rigid pipe, or to make installation easier, use a listed flexible connec- tor if allowed by local codes. Copper may also be used if approved by local codes.
The gas connection at the valve is 3/8" NPT. For minimum and maximum supply pressure see the System Data Table.
System Data - E63-1
(with 38,000 Btu)
For 0 to 2000 feet altitude |
| |
Burner Inlet Orifice Sizes: |
| |
| Natural Gas | Propane |
Burner | #32 | #50 |
*Above 2000 ft. see National Fuel Code Orifice Chart.
Max. Input Rating |
|
|
|
|
Natural Gas | 38,000 Btu/h | |||
Propane | 38,000 Btu/h | |||
Min. Input Rating |
|
|
|
|
Natural Gas | 19,000 Btu/h | |||
Propane | 19,000 Btu/h | |||
|
| |||
Output Capacity with blower Off | ||||
Natural Gas | 27,740 Btu/h | |||
Propane | 28,500 Btu/h | |||
Output Capacity with blower On | ||||
Natural Gas | 28,690 Btu/h | |||
Propane | 29,374 Btu/h | |||
|
|
|
|
|
Supply Pressure |
|
|
|
|
Natural Gas | min. 5.0" w.c. | |||
Propane | min. 12.0" w.c. | |||
|
|
|
|
|
Manifold Pressure |
|
|
|
|
Natural Gas | 3.8" | +/- 0.2" w.c. | ||
Propane | 11" | +/- 0.2" w.c. |
System Data -
For 2,000 - 4,500 feet altitude
Burner Inlet Orifice Sizes:
Natural Gas
Burner #33
Max. Input Rating |
|
Natural Gas | 34,000 Btu/h |
Min. Input Rating |
|
Natural Gas | 17,000 Btu/h |
Output Capacity with blower Off
Natural Gas | 24,820 Btu/h |
Max. Output Capacity with blower On
Natural Gas | 25,670 Btu/h |
System Data -
27,000 Btu (NG) or 29,000 (LP)
For 0 to 4500 feet altitude |
| ||
Burner Inlet Orifice Sizes: |
| ||
| Natural Gas | Propane | |
Burner | #40 |
| #52 |
|
|
| |
Max. Input Rating |
|
| |
Natural Gas | 27,000 Btu/h | ||
Propane |
| 29,000 Btu/h | |
Min. Input Rating |
|
| |
Natural Gas | 13,500 Btu/h | ||
Propane |
| 14,500 Btu/h | |
| |||
Output Capacity with blower Off | |||
Natural Gas | 20,331 Btu/h | ||
Propane |
| 22,330 Btu/h | |
Output Capacity with blower On | |||
Natural Gas | 19,575 Btu/h | ||
Propane |
| 21,518 Btu/h | |
|
|
| |
Supply Pressure |
|
| |
Natural Gas | min. 5.0" w.c. | ||
Propane |
| min. 12.0" w.c. | |
|
|
|
|
Manifold | Pressure |
|
|
Natural Gas | 3.8" +/- 0.2" w.c. | ||
Propane |
| 11" | +/- 0.2" w.c. |
AERATION
ADJUSTMENT
The burner aeration is factory set but may need adjusting due to either the local gas supply, air supply or altitude.
with 38,000 Btu | with 27,000 (NG) / |
| 29,000 LP |
Natural Gas | Natural Gas |
3/8"(9.5mm) | 3/16"(4.75mm) |
Propane | Propane |
wide open | 1/4" (6.35mm) |
|
|
The aeration adjustment gears are located on the right side of the burner box and can be accessed from the side.
To adjust the aeration: use the allen key to turn the turning gear which will adjust the air shut- ter. Open the air shutter for a blue flame or close it for a yellower flame. This adjustment is performed by a qualified installer. The factory setting should be sufficient for most installa- tions.
Clockwise to open,
Caution: Carbon will be produced if the air shutter is closed too much.
Note: Any damage due to carboning resulting from improperly setting the aeration controls is NOT cov- ered under warranty.
Note: Aeration Adjustment should only be performed by an authorized Regency Installer at the time of installation or service.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual
The manifold pressure is controlled by a regu- lator built into the gas control, and should be checked at the pressure test point.
Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.
1)Make sure the valve is in the "OFF" position.