GAS CONNECTION

INSTALLATION

GAS CONNECTION

The gas line can be rigid pipe, or to make installation easier, use a listed flexible connec- tor if allowed by local codes. Copper may also be used if approved by local codes.

The gas connection at the valve is 3/8" NPT. For minimum and maximum supply pressure see the System Data Table.

System Data - E63-1

(with 38,000 Btu)

For 0 to 2000 feet altitude

 

Burner Inlet Orifice Sizes:

 

 

Natural Gas

Propane

Burner

#32

#50

*Above 2000 ft. see National Fuel Code Orifice Chart.

Max. Input Rating

 

 

 

 

Natural Gas

38,000 Btu/h

Propane

38,000 Btu/h

Min. Input Rating

 

 

 

 

Natural Gas

19,000 Btu/h

Propane

19,000 Btu/h

 

 

Output Capacity with blower Off

Natural Gas

27,740 Btu/h

Propane

28,500 Btu/h

Output Capacity with blower On

Natural Gas

28,690 Btu/h

Propane

29,374 Btu/h

 

 

 

 

 

Supply Pressure

 

 

 

 

Natural Gas

min. 5.0" w.c.

Propane

min. 12.0" w.c.

 

 

 

 

 

Manifold Pressure

 

 

 

 

Natural Gas

3.8"

+/- 0.2" w.c.

Propane

11"

+/- 0.2" w.c.

System Data -

HIGHELEVATION:E63-NG1

For 2,000 - 4,500 feet altitude

Burner Inlet Orifice Sizes:

Natural Gas

Burner #33

Max. Input Rating

 

Natural Gas

34,000 Btu/h

Min. Input Rating

 

Natural Gas

17,000 Btu/h

Output Capacity with blower Off

Natural Gas

24,820 Btu/h

Max. Output Capacity with blower On

Natural Gas

25,670 Btu/h

System Data -

E63-1 converted to

27,000 Btu (NG) or 29,000 (LP)

For 0 to 4500 feet altitude

 

Burner Inlet Orifice Sizes:

 

 

Natural Gas

Propane

Burner

#40

 

#52

 

 

 

Max. Input Rating

 

 

Natural Gas

27,000 Btu/h

Propane

 

29,000 Btu/h

Min. Input Rating

 

 

Natural Gas

13,500 Btu/h

Propane

 

14,500 Btu/h

 

Output Capacity with blower Off

Natural Gas

20,331 Btu/h

Propane

 

22,330 Btu/h

Output Capacity with blower On

Natural Gas

19,575 Btu/h

Propane

 

21,518 Btu/h

 

 

 

Supply Pressure

 

 

Natural Gas

min. 5.0" w.c.

Propane

 

min. 12.0" w.c.

 

 

 

 

Manifold

Pressure

 

 

Natural Gas

3.8" +/- 0.2" w.c.

Propane

 

11"

+/- 0.2" w.c.

AERATION

ADJUSTMENT

The burner aeration is factory set but may need adjusting due to either the local gas supply, air supply or altitude.

with 38,000 Btu

with 27,000 (NG) /

 

29,000 LP

Natural Gas

Natural Gas

3/8"(9.5mm)

3/16"(4.75mm)

Propane

Propane

wide open

1/4" (6.35mm)

 

 

The aeration adjustment gears are located on the right side of the burner box and can be accessed from the side.

To adjust the aeration: use the allen key to turn the turning gear which will adjust the air shut- ter. Open the air shutter for a blue flame or close it for a yellower flame. This adjustment is performed by a qualified installer. The factory setting should be sufficient for most installa- tions.

Clockwise to open,

counter-clockwise to close.

Caution: Carbon will be produced if the air shutter is closed too much.

Note: Any damage due to carboning resulting from improperly setting the aeration controls is NOT cov- ered under warranty.

Note: Aeration Adjustment should only be performed by an authorized Regency Installer at the time of installation or service.

GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pres- sures over 1/2 psig (14" w.c.).

The manifold pressure is controlled by a regu- lator built into the gas control, and should be checked at the pressure test point.

Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.

1)Make sure the valve is in the "OFF" position.