Waterford Appliances E63-NG1 Draft Hood, High Elevation, Venting, Vent Terminations

Models: E63-NG1

1 24
Download 24 pages 758 b
Page 8
Image 8
DRAFT HOOD

INSTALLATION

9) Connect green power cord ground wire to

grounding lug.

10) Run neutral black wire from power cord

and connect to fan motor.

11) Run live black wire from power cord and

connect to speed control wire.

12) Connect the white wire of the wire har-

ness to the fan terminal.

DRAFT HOOD

This heater has a draft hood built in. It must not be altered, obstructed, or blocked in any way, and the unit must be installed so that the draft hood is in the same atmospheric pressure zone as the combustion air inlet to the burner. This heater must be properly connected to a venting system. This heater is equipped with a vent safety shutoff system.

WARNING: Operation of this heater when not connected to a properly installed and maintained venting system or tampering with the vent safety shutoff system can result in carbon monoxide (CO) poisoning and possible death.

not penetrate the inner sleeve of the B-Vent when tightening the screw.

Follow all venting manufacturer’s requirements and local building codes. In cold climates, we recommend the use of insulated B-vent, chase, and liners. For altitudes above 2000 ft. we recommend that a minimum flue height of 12 ft. is used.

Vent Terminations

NOTE: Pull excess wire next to fan to

avoid excessive heat from the fire-

box.

13) Ensure all wires are pulled away from

firebox to avoid excessive heat and se-

cure with stick-on wire clip.

14) Re-attach control panel with 3 screws,

reversing step 1. Re-attach rear access

panel with 6 screws, reversing step 5.

NOTE: When power cord is plugged in, speed control is in the ON posi- tion and stove is burning, allow 10

-15 minutes for the thermodisc (temperature switch) to activate and turn on the Fan automatically.

WARNING:

Electrical Grounding Instructions This appliance is equipped with a three pronged (grounding) plug for your protection against shock haz- ard and should be plugged directly into a properly grounded three- prong receptacle. Do not cut or remove the grounding prong from this plug.

HIGH ELEVATION

The E63-1 (with 38,000 Btu) is approved in Canada for altitude 2000 ft. to 4500 ft. (CAN/ CGA-2.17-M91) with the orifice kit (Part # 591- 975). For Natural Gas installations above 4500 ft. follow current CAN/CGA-B149.1.

In U.S.A., for installations above 2000 ft. refer to current ANSI Z223.1 Sc8-8.1.2a appendix F, for resizing orifice.

VENTING

This heater is a vented appliance and must be connected to a chimney/flue in accordance with the installation codes.

Note: The rear pedestal cover plate is only required when outside air is being used. If using room air for combustion, remove this plate from the back of the pedestal.

For your safety this heater is equipped with a vent safety switch designed to sense incorrect venting and react by shutting down the gas supply. This thermally actuated switch is locat- ed within the draft hood and will detect either a blocked chimney or backdraft condition where the chimney flow has reversed. If this switch shuts the unit down, it indicates a drafting problem that must be identified and rectified without delay - the thermally activated switch must never be bypassed or disconnected as a hazardous or deadly condition can result.

Venting Requirements

A four inch diameter vent is required. B-Vent, Class A or Masonry with an approved liner are all acceptable. For cosmetic or aesthetic pur- poses 6" outer vent can be used as long as an approved inner vent is installed. Fasten but do

Installation into Existing

Woodstove Flue System

1)Clean existing Chimney system.

2)Run an approved 4" flex liner or "B" vent into existing chimney.

Note: See the chimney systems manufac- turer for detailed installation instructions.

8

Waterford E63-1 EMERALD Freestanding Gas Stove

Page 8
Image 8
Waterford Appliances E63-NG1 installation manual Draft Hood, High Elevation, Vent Terminations, Venting Requirements