46 Watlow MINICHEF 2000 Application 5
Auto-tuning Note:
Before auto-tuning Application 5, [teNp1] in the operations menu must first be set to a
value that is typical of your application. (See the Hardware & Software Setup Guide for
information) Then set [tHerl] / [tunE1] to [```on]. After you accept [```on], by
pressing “Enter,” the controller will display [`tunE] while auto-tuning is taking place.
The controller will cancel the auto-tuning process if it cannot be completed in 80 min-
utes. You can cancel the auto-tuning process at any time by pressing either key C or key
D and accepting [``Off], by pressing “Enter,” when it appears.