5 Gas piping continued

Boiler Manual

5 Gas piping continued

2.Support piping with hangers, not by boiler or its accessories.

3.Purge all air from gas supply piping.

4.Before placing boiler in operation, check boiler and its gas connection for leaks.

a.Close manual main shutoff valve during any pressure testing at less than 13" w.c.

b.Disconnect boiler and gas valve from gas supply piping during any pressure testing greater than 13" w.c.

Do not check for gas leaks with

an open flame — use bubble test. Failure to use bubble test or check for gas leaks can cause severe personal injury, death or substantial property damage.

5.Use pipe dope compatible with propane gases.

Apply sparingly only to male threads of pipe joints so that pipe dope does not block gas flow.

Failure to apply pipe dope as detailed above can result in severe personal injury, death or substantial property damage.

Natural Gas:

1.Refer to Table 4 for pipe length and diameter. Base on rated boiler input (divide by 1,000 to obtain cubic feet per hour). Table 4 is only for gas with specific gravity 0.60, with a pressure drop through the gas piping of 0.30" w.c. For additional gas pipe sizing information, refer to ANSI Z223.1 (or B149.1 or B149.2 for Canadian installations).

2.Inlet pressure required at gas valve inlet:

Maximum: 13" w.c.

Minimum: 5" w.c.

Manifold gas pressure: 3.5" w.c.

3.Install 100% lockup gas pressure regulator in supply line if inlet pressure exceeds 13" w.c.

￿￿￿￿￿￿￿￿￿￿￿￿Adjust for 13" w.c. maximum.

1.Contact gas supplier to size pipes, tanks and 100% lockup gas pressure regulator.

2.Adjust propane supply regulator provided by gas supplier for 13" w.c. maximum pressure.

3.Inlet pressure required at gas valve inlet:

Maximum: 13" w.c.

Minimum: 11" w.c.

Manifold gas pressure: 10" w.c.

Table 4 Pipe capacity for 0.60 specific gravity natural gas

 

Gas pipe

 

Capacity of pipe for pipe size of:

 

 

 

(Capacity in cubic feet gas per hour)

 

 

length

 

 

 

 

 

 

 

 

 

(feet)

½"

¾"

1"

1¼"

1½"

 

 

 

 

 

 

 

 

 

 

10

132

278

520

1050

1600

 

 

 

 

 

 

 

 

20

92

190

350

730

1100

 

 

 

 

 

 

 

 

30

73

152

285

590

860

 

 

 

 

 

 

 

 

40

63

130

245

500

760

 

 

 

 

 

 

 

 

50

56

115

215

440

670

 

 

 

 

 

 

 

 

75

45

93

175

360

545

 

 

 

 

 

 

 

 

100

38

79

150

305

460

 

 

 

 

 

 

 

 

150

31

64

120

250

380

 

 

 

 

 

 

 