Boiler Manual
typical piping — multiple-zone installations
Figure 6
Zoning with circulators
— return water 130 °F or higher.
Figure 7
Zoning with zone valves
— return water 130 °F or higher.
1 |
ZONE 2
ZONE 1
1
2
ZONE 2
ZONE 1
1 | 1 |
2 | 1 |
| 6 |
1 3
13 | 6 |
|
6 6
5
13
Cold 11 water
fill
12
9 | 10 |
1
Cold 11 water
fill
12
| 1 |
| Alternate |
| circulator |
| location |
9 | 10 |
26012
26013
1Boiler isolation (balancing) valves
2Flow/check valve
3System or zone circulator
5Zone valve
6Drain valve
9Relief valve
10 Automatic air vent (with
air vent when using
11Fill valve
12
13Air separator and automatic vent, if used (Note that the fill valve must always be connected to the expansion tank, regardless of location of expansion tank circulator or air separator.
For systems with possible low
Part number | 17 |