Weil-McLain 550-110-260/02002 Boiler Manual, continued, Is boiler System circulator operating?

Models: 550-110-260/02002

1 60
Download 60 pages 48.89 Kb
Page 51
Image 51
Is boiler System circulator operating?

Boiler Manual

continued

CHART 7 — Insufficient heat or no heat to system (POWER light on steady)

Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.

• Has it been at least 5 minutes since setting thermostat to call for heat? If not, wait 5 minutes. Is system heating?

• Is thermostat set to call for heat? Remove thermostat wires at boiler and check continuity across the two wires. If circuit isn't closed, check external thermostat (zone valve, relay, etc.) wiring. Correct problems and retry.

• Reconnect external thermostat wiring at boiler.

Is thermostat circuit closed (continuity across wires)?

No

 

Yes

 

 

 

Is boiler System circulator operating?

No

Yes

Remove CIRCULATOR harness plug from CIRCULATOR plug receptacle (Figure 25, Item 7, page 44). Check with voltmeter across pins of control module receptacle.

Does voltmeter show 120 VAC across pins?

No

Yes

Are all red lights off?

No

Yes

 

 

 

Wait 30 seconds. Are all red lights off?

No

Yes

 

 

 

Replace control module. Retest.

Boiler is in standby.

Set thermostat to call for heat and recheck

operation.

Verify Sequence of operation, Figure 18, page 31.

Replace control

 

Repair/replace

 

module.

 

 

circulator. Retest.

Retest.

 

Repair/replace

 

 

 

 

wiring. Retest.

 

 

 

 

 

 

 

 

 

• Wait 5 minutes.

Is FLAME light on?

Yes

 

 

No

 

 

 

 

 

 

 

 

 

 

• If you have sufficient heat — boiler should be in normal

 

 

 

 

 

 

 

 

 

 

Is LIMIT light on?

 

 

 

 

 

 

operating sequence. (See normal sequence of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation, Figure 18.)

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

Yes

• If you have less than sufficient heat —

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is vent or combustion air piping free of blockage?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check limit switch

 

 

Replace control module.

 

 

No

 

 

 

 

Yes

 

 

 

contacts with continuity

 

 

Retest.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

checker.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correct conditions and

 

Contact your Weil-McLain

 

 

 

Are limit switch contacts

 

 

 

 

 

 

 

 

 

 

 

 

recheck operation.

 

sales representative.

 

 

 

 

closed?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check rollout switch

• See Figure 18, page 31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

Yes

 

 

 

 

 

for normal sequence of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

continuity — is switch

 

operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

closed?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

Yes

• Wait for boiler water to cool to temperature 20 to 30 ˚F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lower than temperature set on limit switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are limit switch contacts closed?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace rollout switch.

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check any other

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Boiler water temperature exceeded

 

If rollout thermal fuse element has

 

 

 

limit controls wired

 

 

 

 

 

setting on limit switch with thermostat

 

opened, determine cause and

 

 

 

 

into the limit

 

 

 

 

 

 

 

 

 

 

Replace

 

calling for heat. Boiler is OK. (See normal

 

correct condition. Failure to do so

 

 

 

circuit. If all are

 

sequence of operation, Figure 18, p. 31.)

 

will cause severe personal injury,

 

 

 

OK, then replace

 

limit switch.

 

 

 

 

 

 

 

• Also check setting on limit switch (should

 

death or substantial property

 

 

 

 

control module.

Retest.

 

 

 

 

 

 

 

be above 140˚F.).

 

damage.

 

 

 

 

 

 

 

Retest.

 

 

 

 

 

 

 

 

 

 

 

 

 

Part number 550-110-260/0200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51

Page 51
Image 51
Weil-McLain 550-110-260/02002 manual Boiler Manual, continued, Is boiler System circulator operating?, Is FLAME light on?