Boiler Manual

Inspect

 

 

 

6. Check inside and around boiler for evidence of any

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

leaks from the boiler. If found, locate source of leaks

 

 

Eliminate all system or boiler leaks. Continual fresh

 

 

 

 

 

 

and repair.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

makeup water will reduce boiler life. Minerals can build

 

 

 

Burners, base and inlet air box

 

 

 

 

 

 

 

up in sections, reducing heat transfer, overheating cast

 

 

 

 

 

iron, and causing section failure. Leaking water may

 

 

 

1. After turning off power to the boiler, remove the inlet

 

 

also cause severe property damage.

 

 

 

 

 

 

 

 

 

 

 

air box top panel (Figure 27, item 13, page 54).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not use petroleum-based cleaning or sealing

 

 

 

2. Inspect gasket (item 14). Replace if necessary.

 

 

 

 

 

3. Inspect burners and all other components in the

 

 

compounds in boiler system. Severe damage to boiler

 

 

 

 

 

will occur, resulting in substantial property damage.

 

 

 

 

 

 

inlet air box and boiler base.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4. If burners must be cleaned, first remove item 4,

 

 

Electrical shock hazard — Turn off power to the boiler

 

 

 

 

 

 

Figure 27, page 54. Access the burner assembly by

 

 

 

 

 

 

 

 

first removing burner baffle, item 4. Then remove

 

 

before any service operation on the boiler except as

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the screws securing the burner tray to the manifold.

 

 

noted otherwise in this instruction manual. Failure to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slide the burner tray out. Then brush and vacuum

 

 

turn off electrical power could result in electrical shock,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the burners thoroughly, making sure all ports are

 

 

causing severe personal injury or death.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

free of debris.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boiler heating surfaces

 

 

 

5. Inspect the slotted jacket cooling openings in the

 

 

 

 

 

 

 

 

bottom left and rear of the base pan (Figure 27,

 

 

1. Disconnect the vent pipe at the boiler inducer outlet

 

 

 

 

 

 

item 1, page 54).

 

 

 

 

 

connection after turning off power to the boiler.

 

 

 

6. Inspect the base insulation. Pay attention to the

 

 

2. Use a bright light to inspect the flue pipe interior

 

 

 

 

 

 

WARNING on page 36 regarding working with

 

 

 

 

 

and inducer interior.

 

 

 

 

 

 

insulation materials. Verify that the insulation is

 

 

3. Inspect the boiler vent outlet area and heating

 

 

 

 

 

 

intact and secure against all four sides of the base.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

surfaces by looking through the opening.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If insulation is damaged or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4. If the vent pipe or inducer interior show evidence

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

displaced, do not operate the boiler.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of soot, follow Cleaning boiler heating surfaces

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace or reposition insulation as

 

 

 

 

 

in this manual section to remove the flue collector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

necessary. Failure to replace

 

 

 

 

 

and clean the boiler if necessary after close

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

damaged insulation can result in a

 

 

 

 

 

inspection of boiler heating surfaces. If there is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fire hazard, causing severe personal

 

 

 

 

 

evidence of rusty scale deposits, check the water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

injury, death or substantial property

 

 

 

 

 

piping and control system to make sure the boiler

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

damage.

 

 

 

 

 

return water temperature is properly maintained

 

 

 

Condensate drain system

 

 

 

 

 

(per this manual).

 

 

 

 

 

5. Reconnect vent to inducer outlet and replace all

 

 

 

1. Inspect condensate drain fittings and tubing. Verify

 

 

 

 

 

boiler components before returning to service.

 

 

 

 

 

 

that condensate can flow freely to drain.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Service . . . . . . . . . .

Inducer motor

1.With boiler power OFF, place a few drops of S.A.E. 20 motor oil in each of the two oil cups.

Use only S.A.E. 20 motor oil to lubricate the inducer motor. Do not use universal household oils. Motor could be damaged, resulting in possible severe property damage.

Part number 550-110-260/0200

Oiled bearing circulators

1.The circulator shipped with the CGs boiler is water-lubricated. No oiling is required.

2.Check other circulators in the system. Oil any circulators requiring oil, following circulator manufacturer’s instructions. Over-oiling will damage the circulator.

37

Page 37
Image 37
Weil-McLain 550-110-260/02002 manual Burners, base and inlet air box, Boiler heating surfaces, Condensate drain system

550-110-260/02002 specifications

Weil-McLain is a well-known manufacturer of high-quality heating systems and boiler solutions, and the 550-110-260/02002 model is a testament to the company's commitment to innovation and performance. This particular boiler is designed for commercial and residential applications, providing exceptional heating efficiency and reliability.

One of the standout features of the Weil-McLain 550-110-260/02002 is its robust construction. Built using durable materials, this boiler is engineered to withstand demanding environments while maintaining optimal performance. The unit boasts a high thermal efficiency rating, which translates to lower energy costs and reduced environmental impact. The advanced design ensures that fuel consumption is minimized while delivering consistent heat output.

The Weil-McLain 550-110-260/02002 utilizes a multi-stage burner that enhances combustion efficiency. This feature not only reduces emissions but also improves overall energy use, making it an environmentally friendly choice. The sophisticated control system allows for precise modulation of the burner, ensuring that the boiler operates at peak efficiency under various load conditions.

The boiler is equipped with a user-friendly digital control interface, providing operators with real-time monitoring and diagnostics. This allows for easy adjustments and troubleshooting, which helps to reduce maintenance downtime. The integrated safety features enhance the operational reliability of the unit, ensuring safe operation in any environment.

Another important characteristic of the Weil-McLain 550-110-260/02002 is its adaptability. It can be configured to work with various types of fuel including natural gas and propane, giving users the flexibility to choose the most cost-effective energy source. This versatility also helps to extend the lifespan of the boiler as it can be easily adapted to changing energy needs.

In conclusion, the Weil-McLain 550-110-260/02002 is a high-performance boiler that combines durability, efficiency, and advanced technology. With its robust construction, efficient burner system, and user-friendly controls, it stands out as a reliable heating solution for both commercial and residential applications. The commitment to quality and innovation makes this model a preferred choice for those seeking dependable heating systems. Whether for new installations or replacements, the Weil-McLain 550-110-260/02002 delivers exceptional performance and value.