Boiler Manual
1b Prepare boiler location — clearances
Provide the following clearances:
1.Hot water pipes — at least ½" from combustible materials.
2.Recommended service clearances — See Figure 1.
3.Minimum clearances for tight spaces — See
Figure 2.
Figure 1 Recommended clearances for service
Figure 2 Minimum clearances for tight spaces
Flooring and foundation
FlooringThe CGs boiler is approved for installation on combustible flooring, but must never be installed on carpeting.
Do not install boiler on carpeting even if foundation is used. Fire can result, causing severe personal injury, death or substantial property damage.
FoundationProvide a solid brick or minimum
•floor can become flooded.
•the boiler mounting area is not level. The minimum foundation size is 25" long by:
Boiler model number | Width — Inches |
15 | |
|
|
18 | |
|
|
21 | |
|
|
24 | |
|
|
Residential garage installation
PrecautionsTake the following special precautions when installing the boiler in a residential garage. If the boiler is located in a residential garage, per ANSI Z223.1, paragraph 5.1.9:
•Mount the boiler a minimum of 18 inches above the floor of the garage to assure the burner and ignition devices will be no less than 18 inches above the floor.
•Locate or protect the boiler so it cannot be damaged by a moving vehicle.
Part number | 7 |