• Installation •
16 Make final adjustments (continued)
Figure 35 Flue damper assembly, typical
Skim steam boilers:
Determine if water treatment is needed (water boilers only):
Do not use
Continual
For unusually hard water areas or low pH conditions (less than 7.0) consult local water treatment company.
Freeze protection (when used):
1.Use antifreeze especially made for hydronic systems. Inhibited propylene glycol is recommended.
Do not use automotive, ethylene glycol or undiluted antifreeze. Severe personal injury or death can result.
2.50% solution provides protection to about
3.Local codes may require
Clean all newly installed steam boilers to remove oil. Failure to properly clean can result in violent water level fluctuations, water passing into steam mains, or high maintenance costs on strainers, traps and vents. Skim boiler only. Do not clean old piping or leaks can occur.
Do not use
1.Remove 1½" plug from skim tapping tapping “A” – Figure 28, page 29). Provide 1½" skim piping from tapping to floor drain (pipe to side of boiler).
2.Raise waterline to midpoint of skim piping.
3.Fire burner to maintain temperature below steaming rate during skimming process.
4.Feed in water to maintain water level. Cycle burner to prevent rise in steam pressure.
5.Continue skimming until discharge is clear. This may take several hours.
6.Drain boiler. While boiler is warm but not hot, flush all interior surfaces under full pressure until drain water runs clear.
7.Remove skim piping.
8.Close drain cock. Fill with fresh water to normal water line. Start burner and steam for 15 minutes to remove dissolved gases. Stop burner.
9.Check traps and air vents for proper operation.
4.Determine quantity according to system water content. Boiler water content is listed on page 34. Percent of solution will affect sizing of heat distribution units, circulator and expansion tank.
5.Follow antifreeze manufacturer's instructions.
Check boiler for gas-tight seal:
Boiler must be sealed
1. Remove boiler jacket side and top panels.
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per instructions on page 38 of this manual. Failure to comply could result in severe personal injury.
2.Start burner. Observe all sealing points and chalk mark any not
3.To seal all
a.use silicone sealant on section flueways.
b.check gaskets and sealing rope placement.
4.Reinstall all jacket panels.
Part No. | 33 |