Time Delay
The time delay is 5 minutes long. The delay helps to protect the compressor from short cycling in case the power to the heat pump is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.
Pressure Switch Circuit
The defrost control includes
Adjust Defrost System
Defrost Control Board
Optional high pressure switch connections
NOTE: To add the pressure switch, remove the
| P1 |
| FAN |
A | 30 |
|
|
60 | C2 |
| |
| 90 | K1 Relay | |
|
|
|
TEST
terminals. See “Defrost Control Board” in the “Adjust Defrost System” section.
During a single demand cycle, the defrost control will lock out the heat pump after the fifth time that the circuit is interrupted by any pressure switch wired to the control board. In addition,
the diagnostic LEDs will indicate a
B
C | P5 | U1 | U2 |
| |||
|
|
D
DS1
DS2
K2 Relay
P2
H
The heat pump will remain locked out until power to the board is interrupted, then
NOTE: The defrost control board ignores input from the low pressure switch terminals during:
■ | TEST mode |
■ | Defrost cycle |
E
DF
F | C5 |
LW1 C
24V L I
R
O
Y1
■ | |
■ | First 90 seconds after the reversing valve switches heat/cool |
| modes |
NOTE: If the TEST pins are jumpered and the
Defrost Control Board Diagnostic LEDs
| Green | Red LED |
Mode | LED (DS2) | (DS1) |
|
|
|
No Power to Board | Off | Off |
|
| |
Normal Operation/Power to Board | Simultaneous Slow Flash | |
|
| |
Short Cycle Lockout | Alternating Slow Flash | |
|
|
|
Low Pressure Switch Fault | Off | Slow Flash |
|
|
|
Low Pressure Switch Lockout | Off | On |
|
|
|
High Pressure Switch Fault | Slow Flash | Off |
|
|
|
High Pressure Switch Lockout | On | Off |
|
|
|
G
| P6 |
TST PS DF C R O Y1 | |
A. Defrost time setting pins | F. Defrost thermostat |
B. Test pins | G. High pressure switch (optional) |
C. Compressor delay pins | H. Diagnostic LEDs |
D. Reversing valve | I. Low voltage terminal strip |
E. Low pressure switch (optional) | connections |
Adjust Time Between Defrost Cycles
WARNING
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
1.Disconnect power.