SEQUENCE OF OPERATION

Cooling Cycle

Upon cooling demand, the thermostat closes circuit R to O and Y. Closing R to O and Y energizes the reversing valve for cooling operation and closes the heat pump contactor, starting the compressor and outdoor fan. The thermostat automatically closes R to G circuit, which also brings on the indoor fan at the same time. Upon satisfying cooling demand, the thermostat will open the above circuits and open the main contactor, stopping the compressor and outdoor fan. If the indoor unit is equipped with a delay timer, the blower will continue to operate for 60 to 90 seconds, which improves system efficiency.

Heating Cycle

Upon heating demand, the thermostat closes circuit R to Y, which closes the heat pump contactor, starting the compressor and outdoor fan. The reversing valve is not energized in the heating mode. The thermostat again automatically brings on the indoor fan at the same time. Upon satisfying heating demand, the thermostat opens the above circuits and stops heat pump operation.

Defrost Cycle

If the outdoor ambient conditions are such that frost forms on the outdoor coil, the defrost control monitors a defrost cycle. It then runs the defrost cycle as ambient temperatures require.

The defrost control is time/temperature initiated and temperature terminated with a maximum defrost time (time-out) of 10 minutes. The time between defrost cycles is preset at 60-minute intervals at the factory, but can be field adjusted between 30, 60, or

90 minutes. To adjust the time period between defrost cycles, see “Adjust Time Between Defrost Cycles.”

The defrost control will initiate a defrost cycle when the selected time period has elapsed and the defrost sensor sees a temperature below freezing. At the start of a defrost cycle, the defrost control will energize the reversing valve solenoid, shifting the reversing valve and de-energizing the outdoor fan. The defrost relay will also close, energizing temporary heat for increased comfort during defrost (if the indoor unit is so equipped). The heat pump will remain in defrost until the defrost sensor has determined that the frost has been removed from the coil or a 10-minute period has elapsed, whichever comes first.

Defrost Thermostat

The defrost thermostat is located on the liquid line between the check/expansion valve and the distributor. When defrost thermostat senses 42ºF or cooler, the thermostat contacts close and send a signal to the defrost control board to start the defrost timing. It also terminates defrost when the liquid line warms up to 70ºF.

Defrost Control

The defrost control board includes the combined functions of the time/temperature defrost control, defrost relay, diagnostic LEDs and terminal strip for field wiring connections. See “Defrost Control Board” in the “Adjust Defrost System” section.

The control provides automatic switching from normal heating operation to defrost mode and back. During compressor cycle (call for defrost), the control accumulates compressor run times at 30, 60 or 90 minute field-adjustable intervals. If the defrost thermostat is closed when the selected compressor run time interval ends, the defrost relay is energized and defrost begins.

Defrost Control Timing Pins

Each timing pin selection provides a different accumulated compressor run time period during one thermostat run cycle. This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (T1), 60 (T2) or 90 (T3) minutes. See “Defrost Control Board” in the “Adjust Defrost System” section. The defrost timing jumper is factory-installed to provide a 60-minute defrost interval. If the timing selector jumper is not in place, the control defaults to a 90-minute defrost interval. The maximum defrost period is 14 minutes and cannot be adjusted.

A test option is provided for troubleshooting. The test mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the test position at power-up, the control will ignore the test pins. When the jumper is placed across the Test pins for 2 seconds, the control will enter the defrost mode. If the jumper is removed before an additional 5-second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the additional 5-second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and re-applied.

Compressor Delay

The defrost board has a field-selectable function to reduce occasional sounds that may occur while the heat pump is cycling in and out of the defrost mode. The compressor will be cycled off for 30 seconds while going in and out of the defrost mode when the compressor delay jumper is removed.

NOTE: The 30-second “off” cycle is not functional when jumpering the TEST pins.

12

Page 12
Image 12
Whirlpool W4GH6 installation instructions Sequence of Operation, Cooling Cycle, Heating Cycle, Defrost Cycle

W4GH6 specifications

The Whirlpool W4GH6 is a cutting-edge refrigerator designed to meet the demands of modern households. With its sleek design and advanced features, it stands out as a reliable appliance that combines functionality with style.

One of the main features of the W4GH6 is its generous storage capacity. This refrigerator provides ample space for all your food storage needs, ensuring that you can store everything from fresh produce to large party platters without any hassle. The adjustable shelves allow for customizable configurations, accommodating items of various sizes.

Equipped with advanced cooling technologies, the Whirlpool W4GH6 ensures that your food stays fresher for longer. The refrigerator incorporates a multi-air flow system, which efficiently circulates cool air throughout the compartments, maintaining consistent temperatures. This technology helps prevent hotspots and ensures that all items, whether on the top or bottom shelf, receive equal cooling.

Energy efficiency is another hallmark of the W4GH6. It features an Energy Star certification, indicating that it meets strict energy efficiency guidelines set by the US Environmental Protection Agency. This means you can enjoy substantial savings on your energy bills while minimizing your environmental footprint.

The W4GH6 also offers a range of intelligent features designed for user convenience. The refrigerator comes with a temperature management system that allows users to set and monitor temperatures easily. Additionally, its frost-free operation means that you won't have to deal with the hassle of manual defrosting, making maintenance straightforward.

In terms of design, the Whirlpool W4GH6 boasts a modern aesthetic that complements any kitchen décor. The stainless steel finish not only adds a touch of elegance but also resists fingerprints and smudges, ensuring the appliance remains looking pristine.

For families with busy lifestyles, the Whirlpool W4GH6 includes a water and ice dispenser, providing easy access to chilled water and ice on demand. This feature is particularly convenient for hydration during hot days or for quickly preparing drinks for guests.

In summary, the Whirlpool W4GH6 is a versatile refrigerator that excels in both performance and style. Its spacious interior, advanced cooling technologies, and energy-efficient design make it a perfect choice for anyone looking to upgrade their kitchen appliances. With user-friendly features and a contemporary look, the W4GH6 is tailored to enhance your culinary experience while keeping your food fresher for longer.