1.Disconnect power.
2.Remove the refrigerant from the existing system per the manufacturer’s instructions provided with the recovery system being used. Connect the
3.Disconnect the liquid and vapor lines from the existing outdoor unit.
4.Remove the existing outdoor unit.
5.Set the new
6.Remove the existing
Thermal Expansion Valve
A
A. Thermal expansion valve |
| |
Orifice |
|
|
A |
| C |
|
| D |
|
| E |
B | G | F |
|
| |
A. Distributor fitting | E. Orifice extension stub |
|
B. Mounting flange | F. 0.812" brass hex nut |
|
C. Piston orifice | G. Brass hex fitting |
|
D. Ring seal (supplied) |
|
|
7.Remove the caps from the suction and liquid pressure taps.
8.Remove the valve cores.
A
B
A. Suction pressure tap
B. Liquid pressure tap
9.Connect an
10.Connect the
11.Set the recovery machine for liquid recovery and start the recovery machine in accordance with the manufacturer’s instructions provided with the recovery system being used.
12.Open the gauge set valves to allow the recovery machine to run until a vacuum level less than 0" Hg (gauge pressure) is established in the existing system line set and indoor coil.
13.Invert the cylinder of clean
14.After all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery to allow the recovery machine to run until a vacuum level less than 0" Hg (gauge pressure) is established in the existing system line set and indoor coil in accordance with the manufacturer’s instructions provided with the recovery system being used.
NOTE: A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor coil. A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil were removed during the first flush. A second flushing may be required to ensure that the maximum amount of oil is removed.
15.Close the valves on the inverted
16.Remove the recovery machine, gauges,
5